{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0CA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0CA10","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0CA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0CA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV1011-0CA10, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw-type terminals, DIN rail mount.","salesMarkdown":"It provides coordinated protection against overload, short circuit, and phase loss for three-phase motors up to 690 V rated voltage. The 45 mm width and 75 mm depth keep it compact for crowded enclosures. Clearance: 20 mm above and below, 9 mm to the side, zero forward or backward — no extra breathing space needed. Screw-type terminals on the main current circuit accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire. M3 terminal screws for the main contacts.","metaTitle":"Siemens 3RV1011-0CA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV1011-0CA10 SIRIUS motor protection circuit breaker, Trip Class 10, 100 kA breaking capacity at 400 V. Current lifecycle stage. Available to order; RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"None required","at 500 V":"None required","at 690 V":"None required","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.25 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.25 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.25 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"0.25 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.25 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"3.3 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.18 ... 0.25 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d9d2cbef7f50d847f10082ed015f56b6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=427675&mlfb=3RV1011-0CA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0CA10/alternatives.json"},"ai":{"faq":[{"question":"What is 3RV1011-0CA10's depth and width?","answer":"Depth is 75 mm, width is 45 mm, height is 90 mm. Fits standard 45 mm-wide DIN-rail footprint."},{"question":"Will 3RV1011-0CA10 drop into a panel specified for 3RV1011-0GA10?","answer":"Both share the same SIRIUS motor protection circuit breaker platform, same 45 mm width, same DIN-rail mounting, and same terminal layout. The 0GA10 variant carries a different current rating range; verify the motor FLA matches the 0CA10's setting range before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0CA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0CA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}