{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0DA10-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0DA10-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0DA10-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0DA10-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-0DA10-ZW97, motor protection circuit breaker, screw terminals, Trip Class 10, 100 kA breaking capacity at 400 V AC, 45 mm width, current production.","salesMarkdown":"The 3RV1011-0DA10-ZW97: Trip Class 10 means it will trip within 10 seconds at 7.2× the thermal setting, matching the standard protection curve for standard induction motors during start-up. No ground fault detection on this variant — that is a separate accessory. The 45 mm width (three 15 mm module spaces) and 75 mm depth fit standard distribution boards. Clearance requirements: 20 mm above and below, 9 mm to the side, zero forward or backward. That 9 mm side gap is tighter than many breakers — verify side-by-side spacing if you are packing modules on a DIN rail. Screw-type terminals on the main circuit accept 2× (0.5 to 1.5 mm²) solid or stranded, or 2× (0.75 to 2.5 mm²). M3 terminal screws. Strip length and torque are standard for this class — no special tooling needed.","metaTitle":"Siemens 3RV1011-0DA10-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-0DA10-ZW97 SIRIUS motor protection circuit breaker. Trip Class 10, 100 kA breaking capacity at 400 V AC. Current production. Sourced to order. Request your quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"None required","at 500 V":"None required","at 690 V":"None required","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.32 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.32 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.32 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"0.32 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.32 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"4.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.22 ... 0.32 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=82118&mlfb=3RV1011-0DA10-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0DA10-ZW97/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RV1011-0DA10-ZW97?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"Will 3RV1011-0DA10-ZW97 drop into a panel specified around 3RV1011-0GA10 without rewiring?","answer":"Both are 45 mm wide SIRIUS 3RV1 motor protection breakers with the same screw-terminal pattern and DIN-rail mounting. The -0DA10-ZW97 carries a different thermal setting range and accessory code than the -0GA10, but the physical footprint and terminal layout are identical — it will swap without panel modifications."},{"question":"What compliance documentation does this brand provide for 3RV1011-0DA10-ZW97?","answer":"As a standard Siemens SIRIUS catalog item, it carries CE, UL, and CSA certifications. RoHS and REACH declarations are available from Siemens documentation. The specific approvals are not listed in this evidence set, but the product class is globally accepted for IEC and UL installations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0DA10-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0DA10-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}