{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0EA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0EA10","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0EA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0EA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-0EA10 motor protection circuit breaker, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw and snap-on 35 mm DIN rail mount, phase failure detection, 45 mm wide.","salesMarkdown":"The Siemens 3RV1011-0EA10 is a SIRIUS motor protection circuit breaker designed specifically for motor protection duty, with a Class 10 trip characteristic that clears overloads within 10 seconds at 7.2× rated current — fast enough to protect standard induction motors during stall or jam conditions. Rated breaking capacity hits 100 kA at 400 V AC (and at 240 V, 500 V, and 690 V as well), meaning it can safely interrupt a bolted fault up to that level without upstream fuses — useful for high-fault panels where SCCR coordination matters. It includes phase failure detection, so a lost phase on a three-phase motor triggers a trip rather than letting the motor single-phase and overheat. Footprint is 45 mm wide × 90 mm high × 75 mm deep, with 20 mm clearance needed above and below, 9 mm to the side, and zero forward or backward clearance required — tight-panel friendly. Main circuit connections use screw-type terminals accepting 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²) solid or stranded — standard M3 screws, no special tooling. Lifecycle stage is current; no end-of-life notice or last-time-buy date.","metaTitle":"Siemens 3RV1011-0EA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV1011-0EA10 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA breaking capacity at 400 V, screw/snap-on DIN rail mount, phase failure detection, current life","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"None required","at 500 V":"None required","at 690 V":"None required","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.4 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.4 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.4 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"0.4 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.4 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"5.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.28 ... 0.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/21db09360e150d5c8cb07820692533ca.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=164667&mlfb=3RV1011-0EA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0EA10/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV1011-0EA10 drop into a panel built for 3RV1011-0GA10?","answer":"Yes — same 45 mm width, same 35 mm DIN rail mount, same screw terminal pattern. The 0GA10 variant differs in its rated current range and possibly auxiliary contact configuration, but the mechanical footprint is identical."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0EA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0EA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}