{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0EA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0EA15","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0EA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0EA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV1011-0EA15, Class 10 trip, 100 kA breaking capacity at 400 V, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"The Siemens 3RV1011-0EA15 is a SIRIUS motor-protective circuit breaker with a Class 10 trip characteristic, sized for 45 mm width on a 35 mm DIN rail (DIN EN 60715). The 45 mm width and 75 mm depth fit standard motor-starter slots in a SIRIUS lineup. ## Trip class and breaking capacity Class 10 trip means it clears a stalled-rotor condition within 10 seconds at 7.2× setting — the standard for standard-duty motor starting. The 100 kA breaking capacity at 400 V (and at 690 V) gives you full selectivity with a 100 kA SCCR-rated upstream feeder breaker; no need to oversize the branch. ## Environmental and auxiliary ratings Rated for -20 to +60 °C operating ambient, with storage down to -50 °C. The auxiliary contact block switches 1 A at 24 V and 2 A at 120 V — enough for a PLC input or a contactor coil in the same panel.","metaTitle":"Siemens 3RV1011-0EA15 SIRIUS Circuit Breaker, 100 kA at 400","metaDescription":"Siemens 3RV1011-0EA15 SIRIUS motor-protective circuit breaker. 100 kA breaking capacity at 400 V, Class 10 trip. Screw/snap-on 35 mm DIN rail. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Note":"1","Depth":"75 mm","Width":"45 mm","title":"3RV1011-0EA15","Height":"90 mm","Upwards":"20 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 110 V":"2 A","at 120 V":"2 A","at 125 V":"2 A","at 230 V":"0.5 A","at 240 V":"none required","at 400 V":"None required","at 500 V":"None required","at 690 V":"None required","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for motor protection, CLASS 10 A-release 0.28...0.4 A N-release 5.2 A Screw terminal Standard switching capacity with transverse auxiliary switch 1 NO+1 NC","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.4 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.4 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.4 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"0.4 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.4 A","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"5.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.28 ... 0.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$41.15","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3e29ed0f6ebd5eb06e56b8cf7af9f977.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=170920&mlfb=3RV1011-0EA15"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV1011-0EA15 at 400 V?","answer":"100 kA at 400 V, which covers most industrial service-entrance fault levels."},{"question":"What trip class is 3RV1011-0EA15?","answer":"Class 10 — clears a stalled-rotor condition within 10 seconds at 7.2× setting."},{"question":"Will 3RV1011-0EA15 drop into a panel specified around 3RV1011-0GA10?","answer":"Yes — same 45 mm width, same 35 mm DIN-rail footprint, same Class 10 trip. The 0GA10 variant has a different adjustment range, but the mechanical fit is identical."},{"question":"How do I get current pricing and availability for 3RV1011-0EA15?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0EA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0EA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}