{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0FA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0FA10","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0FA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0FA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-0FA10, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw terminals, 45 mm wide, snap-on DIN rail.","salesMarkdown":"Rated breaking capacity hits 100 kA at 240 V, 400 V, 500 V, and 690 V AC — that is the same high-interrupt rating across the common industrial voltages, so it clears faults without cascading upstream on most distribution panels. At 230 V it carries a 0.1 kW motor load; at 480 V and 600 V the continuous current rating is 0.5 A, which sizes it for small motors or light-duty drives. Dimensions: 45 mm wide, 90 mm high, 75 mm deep. Clearance requirements: 20 mm upwards, 20 mm downwards, 9 mm at the side, 0 mm forwards and backwards — so it fits tightly in a shallow enclosure. Main circuit terminals accept 2x (0.5…1.5 mm²) or 2x (0.75…2.5 mm²) solid or stranded wire, M3 screw terminals. ## Environmental and protection features Rated voltage range 20…690 V. Maximum switching frequency in AC-3 duty is 15 operations per hour.","metaTitle":"Siemens 3RV1011-0FA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV1011-0FA10 SIRIUS motor protection circuit breaker, Class 10, 100 kA breaking capacity at 400 V, screw terminals, snap-on DIN rail. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"None required","at 500 V":"None required","at 690 V":"gL/gG 4 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.5 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.5 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"0.5 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.5 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"6.5 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.35 ... 0.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4ac66bbd0d54a002909b88cf2ba90ea3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=135761&mlfb=3RV1011-0FA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0FA10/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RV1011-0FA10?","answer":"Submit an RFQ through this page. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here."},{"question":"What is the closest functional second-source for 3RV1011-0FA10?","answer":"The 3RV1011-0GA10 is a peer in the same SIRUS series with identical dimensions and mounting, but its trip curve and breaking capacity differ — verify coordination before substituting."},{"question":"Will 3RV1011-0FA10 drop into a panel specified around 3RV1011-0GA10 without rewiring?","answer":"Yes, both share the same 45 mm width, 90 mm height, 75 mm depth, and snap-on DIN rail mounting, so the footprint is identical. Terminal layout and screw size are the same, so no rewiring is needed for the panel cutout."},{"question":"What compliance documentation does Siemens provide for 3RV1011-0FA10?","answer":"Siemens typically provides RoHS, REACH, UL, and IEC declarations for the SIRIUS series. Specific certificates are available on request via the RFQ process."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0FA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0FA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}