{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0FA10-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0FA10-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0FA10-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0FA10-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-0FA10-ZW98 motor protection circuit breaker, 100 kA breaking capacity at 400 V, Trip Class 10, phase failure detection, screw-type terminals, 45 mm width.","salesMarkdown":"The 100 kA breaking capacity at 400 V (and at 240 V, 500 V, and 690 V) means this device can safely interrupt fault currents up to that level without cascading upstream, which is the figure that governs panel SCCR coordination. Screw-type terminals on the main current circuit accept 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²). The M3 terminal screws for the main contacts are sized for control wiring. Clearance requirements: 20 mm upwards and downwards, 9 mm at the sides, zero forwards and backwards — tight panel packing is possible.","metaTitle":"Siemens 3RV1011-0FA10-ZW98 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-0FA10-ZW98 motor protection circuit breaker. 100 kA breaking capacity at 400 V, Trip Class 10, phase failure detection. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"None required","at 500 V":"None required","at 690 V":"gL/gG 4 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.5 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.5 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"0.5 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.5 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"6.5 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.35 ... 0.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=90343&mlfb=3RV1011-0FA10-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0FA10-ZW98/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV1011-0FA10-ZW98?","answer":"100 kA at 240 V, 400 V, 500 V, and 690 V AC — the same high interrupting rating across the common industrial voltage bands, which simplifies panel SCCR coordination."},{"question":"Where can I buy 3RV1011-0FA10-ZW98?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What does Trip Class 10 mean for motor protection?","answer":"Trip Class 10 means the breaker will trip within 10 seconds at 7.2× the thermal setting — matched to standard induction motor starting profiles so it passes the inrush without nuisance tripping."},{"question":"Does 3RV1011-0FA10-ZW98 detect phase failure?","answer":"Yes, phase failure detection is built in — a single-phased motor sees a trip rather than a burn-out."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0FA10-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0FA10-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}