{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0GA10-0FJ0-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0GA10-0FJ0-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0GA10-0FJ0-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0GA10-0FJ0-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-0GA10-0FJ0-ZX95, 0.63 A rated continuous current, Class 10 trip class, 100 kA breaking capacity at 400 V AC, screw-type terminals, 45 mm width.","salesMarkdown":"Any mounting position is allowed. Terminals are screw-type, accepting solid and stranded conductors up to 2.5 mm² (or 2x 1.5 mm²), and AWG 18–14 for the main circuit. An auxiliary switch is present on this variant, so you can wire a status feedback to the PLC without an add-on block. The base variant 3RV1011-0GA10 (without the -0FJ0-ZX95 suffix) is the same motor protection breaker without the factory-fitted auxiliary switch. If the auxiliary contact is not needed for your application, that version drops into the same footprint without rewiring — same 45 mm width, same DIN rail mount, same terminal layout. The -1HA10 variant steps up to a higher current range; verify the motor FLA before substituting. ## Panel Integration & Environment Dimensions: 45 mm wide, 90 mm high, 81 mm deep. The 45 mm width matches a standard 2.5-module DIN rail footprint, so it occupies two 18 mm slots on a 35 mm rail. Zero side and zero backwards clearance means you can abut it against adjacent devices or the enclosure wall — no breathing gap needed. Shock rated at 25g for 11 ms — suitable for machine-mounted panels on presses or conveyors. Mechanical endurance of the main contacts is 100 000 cycles typical. Maximum switching frequency under AC-3 duty is 15 operations per hour.","metaTitle":"Siemens 3RV1011-0GA10-0FJ0-ZX95 SIRIUS Motor Protection Circ","metaDescription":"Siemens SIRIUS 3RV1011-0GA10-0FJ0-ZX95 motor protection circuit breaker, 0.63 A rated current, Class 10 trip, 100 kA breaking capacity at 400 V. Current production. Quoted on reque","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","Maximum":"2 000 m","Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Backwards":"0 mm","Trip class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","On The Front":"IP20","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","Auxiliary switch":"Yes","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Shock resistance":"25g / 11 ms","Mounting position":"any","Product brand name":"SIRIUS","Product designation":"circuit breaker","at 400 V rated value":"0.18 kW","Design of the product":"for motor protection","For Auxiliary Contacts":"0","Ground fault detection":"No","Phase failure detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","Continuous current rated value":"0.63 A","at AWG conductors for main contacts":"2x (18 ... 14)","Surge voltage resistance rated value":"6 000 V","at AC in hot operating state per pole":"1.8 W","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","For Auxiliary And Control Current Circuit":"screw-type terminals","Removable Terminal For Auxiliary And Control Circuit":"No","Design of the overcurrent release and short-circuit release":"thermomagnetic","Arrangement of electrical connectors for main current circuit":"front side","Adjustable pick-up value current of the current-dependent overload release":"0.45 ... 0.63 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=319241&mlfb=3RV1011-0GA10-0FJ0-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0GA10-0FJ0-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Will the 3RV1011-0GA10-0FJ0-ZX95 drop into a panel specified around 3RV1011-0GA10 without rewiring?","answer":"Yes — the base variant 3RV1011-0GA10 shares the same 45 mm width, DIN rail mounting, and screw-type terminal layout. The -0FJ0-ZX95 suffix adds a factory-fitted auxiliary switch, so if your panel already has an auxiliary block wired separately, you may need to adjust the control wiring. Otherwise the footprint and main circuit connections are identical."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0GA10-0FJ0-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0GA10-0FJ0-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}