{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0HA10-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0HA10-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0HA10-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0HA10-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-0HA10-ZW96, motor protection circuit breaker, Class 10, screw-type terminals, 45 mm width, 90 mm height, 75 mm depth, DIN rail snap-on.","salesMarkdown":"The Siemens SIRIUS 3RV1011-0HA10-ZW96 is a motor protection circuit breaker designed for Class 10 trip characteristics, meaning it will trip within 10 seconds at 7.2x the thermal setting. This is the standard protection for standard induction motors starting under load — pumps, conveyors, compressors. It includes phase failure detection, which opens the circuit if one phase drops out, preventing single-phasing damage. Dimensions are 45 mm wide, 90 mm high, 75 mm deep. Requires 20 mm clearance above and below, 9 mm at the sides, zero forward or backward clearance. The screw-type terminals accept 2x (0.5...1.5 mm²) or 2x (0.75...2.5 mm²) solid or stranded wire, terminated with M3 screws on the main contacts. ## Ratings and Application Rated operating voltage range is 20...690 V. Breaking capacity is 100 kA at 240 V, 400 V, 500 V, and 690 V AC. At 230 V, the motor power rating is 0.1 kW. The maximum switching frequency at AC-3 duty is 15 operations per hour.","metaTitle":"Siemens 3RV1011-0HA10-ZW96 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-0HA10-ZW96 motor protection circuit breaker, Class 10 trip, phase failure detection, DIN rail mount, 45x90x75 mm. Active production, sourced to order. RFQ fo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"None required","at 500 V":"gL/gG 6 A","at 690 V":"gL/gG 6 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.8 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.8 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.8 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"0.8 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.8 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.55 ... 0.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=214767&mlfb=3RV1011-0HA10-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0HA10-ZW96/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-0HA10-ZW96 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is the depth of 3RV1011-0HA10-ZW96?","answer":"The depth is 75 mm. The overall dimensions are 45 mm wide, 90 mm high, and 75 mm deep."},{"question":"What trip class does this circuit breaker have?","answer":"It is Class 10, meaning it will trip within 10 seconds at 7.2 times the thermal setting. This is standard for motor starting under load."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0HA10-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0HA10-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}