{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0HA10-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0HA10-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0HA10-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0HA10-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-0HA10-ZW98, Class 10 trip, 100 kA breaking capacity at 400 V AC, 45 mm wide, screw and snap-on DIN rail mount.","salesMarkdown":"## What this SIRIUS breaker does on the line There is no ground fault detection on this variant, so for applications requiring GF protection, you would add an external ground-fault relay or choose a different SIRIUS version. The breaker measures 45 mm wide by 90 mm high by 75 mm deep — a standard 45 mm module that fits directly onto 35 mm DIN rail per DIN EN 60715, using either screw fixing or snap-on mounting. Clearance requirements are minimal: 20 mm upwards, 20 mm downwards, 9 mm to the side, and 0 mm forwards or backwards. That means it fits tightly into a crowded enclosure without extra breathing space. Terminals are M3 screw-type for the main current circuit, accepting 2 × (0.5 to 1.5 mm²) or 2 × (0.75 to 2.5 mm²) solid or stranded wire. ## Fuse coordination and switching frequency At 240 V and 400 V, no upstream fuse is required — the breaker's own breaking capacity handles the fault. Maximum switching frequency is 15 operations per hour under AC-3 and AC-3e duty, which is typical for motor-starting applications — not for frequent jogging or inching cycles.","metaTitle":"Siemens 3RV1011-0HA10-ZW98 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-0HA10-ZW98 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA breaking capacity at 400 V. 45 mm wide, DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"None required","at 500 V":"gL/gG 6 A","at 690 V":"gL/gG 6 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.8 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.8 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.8 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"0.8 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.8 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.55 ... 0.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=519291&mlfb=3RV1011-0HA10-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0HA10-ZW98/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-0HA10-ZW98 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ and we'll get you a firm number."},{"question":"What is the closest functional second-source for the 3RV1011-0HA10-ZW98?","answer":"The base variant 3RV1011-0HA10 is functionally identical — the -ZW98 suffix typically denotes a special version (e.g., custom settings or packaging). For most applications, the standard 3RV1011-0HA10 drops in without rewiring, but verify the specific -ZW98 customization against your BOM before substituting."},{"question":"Will the 3RV1011-0HA10-ZW98 drop into a panel specified around the 3RV1011-0HA10?","answer":"Yes, the dimensions are identical — 45 mm wide, 90 mm high, 75 mm deep — and both use the same screw/snap-on DIN rail mount. The -ZW98 variant shares the same footprint and terminal layout, so it fits without panel modifications."},{"question":"What compliance documentation does Siemens provide for this breaker?","answer":"Siemens typically provides RoHS and REACH declarations, plus UL/CSA/CE/IEC certifications for the SIRIUS series. Specific documentation for the 3RV1011-0HA10-ZW98 should be available through Siemens' support portal or your distributor upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0HA10-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0HA10-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}