{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0JA10-ZW95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0JA10-ZW95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0JA10-ZW95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA10-ZW95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-0JA10-ZW95, 45 mm wide, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw-type terminals, for motor protection.","salesMarkdown":"## Trip Class and Protection Features Rated Trip Class 10, so it trips within 10 seconds at 7.2× the thermal setting — standard for protecting standard induction motors during startup. No ground fault detection on this variant, so if your application requires that, you'd need a separate ground-fault relay or a different SIRIUS model. The 45 mm width and 75 mm depth fit standard panel layouts — it occupies one 45 mm slot on the rail, leaving room for auxiliary contact blocks or a downstream contactor in the same footprint. Clearance requirements: 20 mm above and below, 9 mm to the side, zero forwards or backwards — tight enough for dense panels if you respect the ventilation gaps.","metaTitle":"Siemens 3RV1011-0JA10-ZW95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-0JA10-ZW95 motor protection circuit breaker, 100 kA breaking capacity at 400 V, Trip Class 10, 45 mm wide, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 10 A","at 500 V":"gL/gG 10 A","at 690 V":"gL/gG 10 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1 A","at 500 V rated value":"100 kA","at 600 V rated value":"1 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 575/600 V rated value":"0.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"1 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"1 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=178368&mlfb=3RV1011-0JA10-ZW95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA10-ZW95/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for this part?","answer":"Standard Siemens SIRIUS documentation includes CE, UL, CSA, and CCC certifications. RoHS and REACH declarations are available on request. The part carries the SIRIUS brand and is manufactured under Siemens quality systems."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0JA10-ZW95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0JA10-ZW95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}