{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0JA10-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0JA10-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0JA10-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA10-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-0JA10-ZW96, motor protection circuit breaker, 45 mm width, Trip Class 10, 100 kA interrupting capacity at 400 V, screw-type terminals, snap-on 35 mm DIN rail.","salesMarkdown":"Its Trip Class 10 means it trips within 10 seconds at 7.2× the thermal setting — fast enough to protect standard motors during a locked-rotor event without nuisance tripping on normal starts. The 100 kA interrupting capacity at 400 V (and at 690 V) means it can safely clear a bolted fault on a high-capacity distribution board without upstream fuses needing to coordinate down to a lower let-through. At 45 mm wide and 90 mm tall, it occupies a single module slot in a standard enclosure. The 75 mm depth leaves clearance for wiring behind the gland plate — no forced spacing needed. Screw-type terminals on the main circuit accept 2×(0.5–1.5 mm²) or 2×(0.75–2.5 mm²) solid or stranded copper, so it ties into existing panel wiring without terminal-block adapters.","metaTitle":"Siemens 3RV1011-0JA10-ZW96 SIRIUS Motor Protection CB, 100 k","metaDescription":"Siemens SIRIUS 3RV1011-0JA10-ZW96 motor protection circuit breaker. Trip Class 10, 100 kA SCCR at 400 V, 45 mm wide, snap-on DIN rail. Active production. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 10 A","at 500 V":"gL/gG 10 A","at 690 V":"gL/gG 10 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1 A","at 500 V rated value":"100 kA","at 600 V rated value":"1 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 575/600 V rated value":"0.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"1 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"1 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=429635&mlfb=3RV1011-0JA10-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA10-ZW96/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-0JA10-ZW96 and how do I get a price?","answer":"This part is available to order against an RFQ through our independent distribution channel. Submit a request for a firm quote — availability and current pricing are confirmed at that time."},{"question":"Will 3RV1011-0JA10-ZW96 drop into a panel that was specified around 3RV1011-0HA10 without rewiring?","answer":"Both are 45 mm wide SIRIUS motor protection breakers with the same screw-type terminal and snap-on DIN rail mounting. The 3RV1011-0HA10 carries a different current range, but the footprint and wiring interface are identical — no rewiring needed for the panel layout."},{"question":"What is 3RV1011-0JA10-ZW96's listed depth (75 mm) on this component line?","answer":"The depth is 75 mm. That is the dimension from the DIN rail mounting surface to the front of the housing — standard for this SIRIUS frame size."},{"question":"What is 3RV1011-0JA10-ZW96's listed width (45 mm) on this component line?","answer":"The width is 45 mm, which is the standard single-module width for SIRIUS 3RV1 breakers."},{"question":"What compliance documentation does this brand provide for 3RV1011-0JA10-ZW96 (RoHS, REACH, UL, IEC)?","answer":"The SIRIUS series typically carries UL, CSA, CE, and IEC certifications, and the manufacturer publishes RoHS and REACH declarations. Specific document IDs for this exact order code should be confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0JA10-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0JA10-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}