{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0JA10-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0JA10-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0JA10-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA10-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-0JA10-ZW97, Class 10 trip, 100 kA breaking capacity at 400 V AC, phase failure detection, screw terminals, DIN rail mount.","salesMarkdown":"It also detects phase failure, which is common in field conditions where a blown fuse upstream can single-phase a motor and cook it. ## Breaking capacity — what the 100 kA rating means This breaker carries a 100 kA breaking capacity at 240 V, 400 V, 500 V, and 690 V AC. Clearance requirements: 20 mm upward, 20 mm downward, 9 mm to the side, zero forward or backward. That 9 mm side gap is tighter than some breakers; if you're packing multiple units side-by-side, make sure the enclosure's internal width accounts for it. ## Terminals and wiring Main circuit terminals are screw-type, sized for M3 screws. Accepts two conductors per terminal: 2× (0.5 to 1.5 mm²) solid or stranded, or 2× (0.75 to 2.5 mm²). That's enough for a motor feed cable up to about 2.5 mm² — typical for fractional to small integral horsepower motors. If your motor draw calls for larger wire, step up to the next frame size in the SIRIUS family.","metaTitle":"Siemens 3RV1011-0JA10-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-0JA10-ZW97 SIRIUS motor protection circuit breaker. Class 10 trip, 100 kA breaking capacity at 400 V. Phase failure detection. DIN rail mount. Current production. A","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 10 A","at 500 V":"gL/gG 10 A","at 690 V":"gL/gG 10 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1 A","at 500 V rated value":"100 kA","at 600 V rated value":"1 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 575/600 V rated value":"0.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"1 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"1 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c5324acfeb5e22fb6b4e046898e5a5f2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=454914&mlfb=3RV1011-0JA10-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA10-ZW97/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-0JA10-ZW97 and what is the lead time?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional second-source to 3RV1011-0JA10-ZW97?","answer":"The closest functional peer within the same SIRIUS family is 3RV1011-0HA10. Both are Class 10 motor protection breakers with the same 45 mm width and DIN rail mount. The -0HA10 variant has a different current setting range; verify your motor FLA against the adjustment range before swapping."},{"question":"Will 3RV1011-0JA10-ZW97 drop into a panel specified around 3RV1011-0HA10 without rewiring?","answer":"Yes, the -ZW97 and -HA10 share the same 45 mm width, 75 mm depth, 90 mm height, and DIN rail mount. Terminal type and conductor sizes are identical. No rewiring needed for the mechanical fit — but double-check the current adjustment range matches your motor."},{"question":"What compliance documentation does Siemens provide for 3RV1011-0JA10-ZW97?","answer":"As a SIRIUS product, this breaker carries CE marking for the European market and is designed to meet IEC/EN 60947 standards. Siemens typically provides RoHS and REACH declarations on request through their documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0JA10-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0JA10-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}