{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0JA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0JA15","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0JA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV1011-0JA15, 45 mm wide, Class 10 trip, 100 kA breaking capacity at 400 V, screw and snap-on mounting for 35 mm DIN rail.","salesMarkdown":"It carries a 100 kA breaking capacity at 400 V, 500 V, and 690 V, with a Class 10 trip characteristic — that's the standard thermal-magnetic curve for protecting standard induction motors against overload and short circuit. The 45 mm width fits a standard modular enclosure grid. The same 100 kA holds at 500 V and 690 V, so it covers 480 V and 600 V class systems without derating the interrupt rating. Class 10 trip gives a maximum 10-second trip time at 600% of the thermal setting, matching the heating curve of a standard 4-pole induction motor during a locked-rotor start. The maximum switching rate is 15 operations per hour under AC-3 duty — that's the motor-starting load cycle, so it's not rated for frequent jogging or inching applications. Auxiliary contact ratings span the control-voltage range: 1 A at 24 V, 2 A at 110–125 V, 0.5 A at 230 V. For DC switching, it's 0.15 A at 60 V. The main contact terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire — M3 screw terminals, standard for this class. The depth is 75 mm, height 90 mm, width 45 mm. Clearance distances: 20 mm upwards and downwards, 9 mm at the side, 0 mm forwards and backwards — meaning it can be mounted flush against a panel backplane or adjacent devices on the same DIN rail.","metaTitle":"Siemens 3RV1011-0JA15 SIRIUS Circuit Breaker, 100 kA at 400","metaDescription":"Siemens SIRIUS 3RV1011-0JA15 circuit breaker, 100 kA breaking capacity at 400 V, Class 10 trip, 45 mm wide. Current-production status. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Note":"1","Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 110 V":"2 A","at 120 V":"2 A","at 125 V":"2 A","at 230 V":"0.5 A","at 240 V":"none required","at 400 V":"gL/gG 10 A","at 500 V":"gL/gG 10 A","at 690 V":"gL/gG 10 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1 A","at 500 V rated value":"100 kA","at 600 V rated value":"1 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 575/600 V rated value":"0.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"1 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"1 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=421398&mlfb=3RV1011-0JA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA15/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV1011-0JA15 drop into a panel that was specified around 3RV1011-0GA10 without rewiring?","answer":"Both are 45 mm wide SIRIUS breakers with the same DIN-rail mounting footprint per DIN EN 60715, so the mechanical fit is identical. Terminal wire sizes and M3 screw terminals are the same. Verify the trip setting range on the 0GA10 variant against the 0JA15's rating — the physical swap is straightforward."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0JA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0JA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}