{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0JA20-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0JA20-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0JA20-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA20-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-0JA20-ZW97, 1 A continuous current, CLASS 10 trip class, 100 kA breaking capacity at 400 V, 3-pole, spring-loaded terminals, screw and snap-on 35 mm DIN rail mount.","salesMarkdown":"## Trip Class and Motor Protection The 3RV1011-0JA20-ZW97: Rated CLASS 10, this breaker will trip within 10 seconds at 7.2× the thermal setting. That matches the standard protection requirement for standard squirrel-cage induction motors during a locked-rotor condition. The 100 kA breaking capacity holds across the full voltage range: 240 V, 400 V, 500 V, and 690 V AC. That is a flat high-fault curve, not a derated one at higher voltages. Zero clearance required at the sides and rear — the breaker can be butted directly against adjacent devices and the panel backplate. Front face carries an IP20 rating, so finger-safe when installed in an enclosure. Any mounting position is permitted. Main circuit terminals are spring-loaded, accepting solid conductors 2x (0.25... 2.5 mm²) or finely stranded with ferrule 2x (0.25... 1.5 mm²). AWG equivalents are 2x (24... 14). No screw torque to verify — spring-clamp termination is vibration-resistant and consistent across temperature cycles. Shock rated at 25g for 11 ms. Mechanical endurance is 100 000 cycles on the main contacts.","metaTitle":"Siemens 3RV1011-0JA20-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-0JA20-ZW97 SIRIUS motor protection circuit breaker, 1 A continuous current, CLASS 10 trip, 100 kA breaking capacity at 400 V. Active production. Quoted to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","Maximum":"2 000 m","Backwards":"0 mm","Trip class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","On The Front":"IP20","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","Auxiliary switch":"Yes","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Shock resistance":"25g / 11 ms","Mounting position":"any","Product brand name":"SIRIUS","Product designation":"circuit breaker","at 400 V rated value":"0.25 kW","Design of the product":"for motor protection","For Auxiliary Contacts":"0","Ground fault detection":"No","Phase failure detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","Continuous current rated value":"1 A","at AWG conductors for main contacts":"2x (24 ... 14)","Surge voltage resistance rated value":"6 000 V","at AC in hot operating state per pole":"1.8 W","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","For Auxiliary And Control Current Circuit":"spring-loaded terminals","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Removable Terminal For Auxiliary And Control Circuit":"No","Design of the overcurrent release and short-circuit release":"thermomagnetic","Arrangement of electrical connectors for main current circuit":"front side","Adjustable pick-up value current of the current-dependent overload release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=333703&mlfb=3RV1011-0JA20-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0JA20-ZW97/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3RV1011-0JA20-ZW97 and how is it quoted for volume purchases?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What is 3RV1011-0JA20-ZW97's listed depth?","answer":"The listed depth is 81 mm."},{"question":"What conductor sizes does the spring-loaded terminal accept?","answer":"Solid conductors: 2x (0.25... 2.5 mm²). Finely stranded with ferrule: 2x (0.25... 1.5 mm²). AWG equivalents: 2x (24... 14)."},{"question":"Will 3RV1011-0JA20-ZW97 drop into a panel specified around 3RV1011-0GA10 without rewiring?","answer":"Both parts share the same SIRIUS frame size, 45 mm width, and 35 mm DIN rail mounting with zero side clearance. The terminal type differs — this unit uses spring-loaded terminals versus screw-type on the 0GA10 variant — so verify the wiring method matches your panel's existing terminations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0JA20-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0JA20-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}