{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1AA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1AA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1AA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1AA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1AA10-ZX95 motor protection circuit breaker, Class 10, 100 kA interrupting at 400 V, screw terminals, 45 x 90 x 75 mm, DIN rail mount.","salesMarkdown":"The 45 mm width and 75 mm depth keep it compact for dense MCC or control-panel rows. Trip Class 10 means it clears an overload within 10 seconds at 7.2× rated current — standard for general-purpose motor starting where the inrush doesn't exceed that window. No ground-fault detection on this variant; that's a separate function if your circuit demands it. ## Interrupting capacity and coordination Rated interrupting capacity hits 100 kA at 240 V, 400 V, and 500 V — that's high enough for most industrial service-entrance or sub-distribution panels without needing a current-limiting upstream breaker. At 690 V it drops to 2 kA, so on 690 V systems verify the available fault current stays below that threshold or add a backup fuse. The manufacturer specifies backup fuse requirements: at 400 V use a gL/gG 20 A fuse; at 500 V the same; at 690 V also gL/gG 20 A. At 240 V no backup fuse is required. The 100 kA rating at 400 V means this breaker can safely interrupt a fault up to that level without cascading upstream — a key spec for panel builders coordinating selectivity in a UL 508A or IEC 61439 assembly. ## Termination and environmental limits Main circuit terminals are screw-type, accepting 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded copper. Torque spec for the M3 main-contact screws is standard — no special tooling needed. Operating temperature range is -20 to +60 °C; storage and transport range is -50 to +80 °C, so it handles warehouse and trucking extremes without issue. Clearance spacing: 20 mm upwards and downwards, 9 mm at the sides, 0 mm forwards and backwards. That's tight enough to pack breakers side-by-side in a multi-row panel without excessive gutters.","metaTitle":"Siemens 3RV1011-1AA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-1AA10-ZX95 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA interrupting at 400 V, screw terminals, DIN rail mount. Current production. Quoted to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Trip Class":"CLASS 10","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/603ea4ea7e17212102b9801c8c04fbf9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=221922&mlfb=3RV1011-1AA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1AA10-ZX95/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1AA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1AA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}