{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1AA15-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1AA15-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1AA15-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1AA15-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1AA15-0BA0, motor protection circuit breaker, 1.6 A rated continuous current, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw and snap-on DIN rail mount.","salesMarkdown":"## Motor Protection Circuit Breaker for 0.55 kW Loads The Siemens SIRIUS 3RV1011-1AA15-0BA0 is a motor protection circuit breaker rated for 1.6 A continuous current, sized for a 0.55 kW motor at 400 V AC. ## DIN Rail Mounting and Panel Fit The 45 mm wide, 90 mm tall, 81 mm deep footprint fits a standard 4-module width on the rail, leaving room for a contactor and overload relay in a motor starter lineup. Any mounting position is permitted, so vertical or horizontal rail orientation works. Screw-type terminals on both main and auxiliary circuits accept solid conductors: 2× (0.5…1.5 mm²) and 2× (0.75…2.5 mm²), or stranded equivalents. AWG equivalents for main contacts are 2× (18…14). Zero clearance required at the sides or rear for heat dissipation. Breaking capacity holds at 100 kA across 240 V, 400 V, and 500 V AC, then drops to 2 kA at 690 V AC. Shock rated at 25g for 11 ms. RoHS compliance is documented with a substance prohibition date of 01/01/2013.","metaTitle":"Siemens 3RV1011-1AA15-0BA0 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-1AA15-0BA0 motor protection circuit breaker, 1.6 A continuous, Class 10, 100 kA breaking capacity at 400 V. Current lifecycle stage, sourced to order. RFQ fo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","title":"3RV1011-1AA15-0BA0","Height":"90 mm","at 24 V":"1 A","at 60 V":"0.15 A","Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","at 230 V":"0.5 A","Backwards":"0 mm","Trip Class":"CLASS 10","At The Side":"0 mm","Rated Value":"20 ... 690 V","description":"Special type Circuit breaker size S00 for motor protection CLASS 10 A-release 1.1...1.6 A N-release 21 A Screw terminal Standard switching capacity with transverse auxiliary switch 1 NO+1 NC Ambient temperature -50 °C 500 switching cycles","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-50 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"0.55 kW","Design Of The Product":"for motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"2 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"7.25 W","Substance Prohibitance (Date)":"01/01/2013","Continuous Current Rated Value":"1.6 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","at AWG cables for main contacts":"2x (18 ... 14)","Design Of The Short-Circuit Trip":"magnetic","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AWG cables for auxiliary contacts":"2x (18 ... 14)","at AC in hot operating state per pole":"2.4 W","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","operational current at AC-3 at 400 V rated value":"1.6 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"thermomagnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"21 A","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"500","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/204e199ff10f385251f7c975f7d9be7a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=6518&mlfb=3RV1011-1AA15-0BA0"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-1AA15-0BA0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is the depth of 3RV1011-1AA15-0BA0?","answer":"The depth is 81 mm, with a width of 45 mm and height of 90 mm."},{"question":"What conductor sizes does the 3RV1011-1AA15-0BA0 accept?","answer":"Solid conductors: 2× (0.5…1.5 mm²) and 2× (0.75…2.5 mm²). Stranded: same ranges. AWG for main contacts: 2× (18…14)."},{"question":"Does 3RV1011-1AA15-0BA0 have phase failure protection?","answer":"Yes, phase failure detection is built into the overload release. Ground fault detection is not included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1AA15-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1AA15-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}