{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1AA25","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1AA25","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1AA25","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1AA25","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1AA25 motor protection circuit breaker, 1.6 A rated continuous current, Trip Class 10, 100 kA breaking capacity at 400 VAC, spring-loaded terminals, screw and snap-on DIN rail mount.","salesMarkdown":"## Motor protection circuit breaker, 1.6 A, Class 10 — panel fit and ratings The motor power rating is 0.55 kW at 400 V AC, sized for a small pump or conveyor motor. The 1.6 A continuous rating and Class 10 trip curve mean it will hold starting inrush for standard squirrel-cage motors without nuisance tripping, but will trip within 10 seconds at 7.2× rated current — per the Class 10 definition. ## Termination and wiring — spring-loaded terminals, conductor range Both the main current circuit and auxiliary/control circuit use spring-loaded terminals, accepting 2× (0.25 to 2.5 mm²) solid or 2× (24 to 14 AWG) stranded. ## Environmental limits and surge withstand Shock resistance is 25 g for 11 ms — suitable for machine-mounted panels near rotating equipment.","metaTitle":"Siemens 3RV1011-1AA25 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV1011-1AA25 SIRIUS motor protection circuit breaker, 1.6 A continuous, Trip Class 10, 100 kA breaking at 400 VAC, spring terminals, DIN rail mount, current lifecycle stag","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","at 24 V":"1 A","at 60 V":"0.15 A","at 230 V":"0.5 A","Backwards":"0 mm","Trip Class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"0.55 kW","Design Of The Product":"for motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"2 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"7.25 W","Substance Prohibitance (Date)":"01.01.2013","Continuous Current Rated Value":"1.6 A","Design Of The Auxiliary Switch":"transverse","at AWG cables for main contacts":"2x (24 ... 14)","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"spring-loaded terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AWG cables for auxiliary contacts":"2x (24 ... 14)","at AC in hot operating state per pole":"2.4 W","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","number of CO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"1.6 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"thermomagnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"100 000","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=154731&mlfb=3RV1011-1AA25","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1AA25/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this part carry?","answer":"RoHS compliance is confirmed by the substance prohibition date of 01.01.2013. The part carries the SIRIUS brand designation and is designed per IEC/EN standards for motor protection circuit breakers."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1AA25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1AA25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}