{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1CA10-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1CA10-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1CA10-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1CA10-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-1CA10-ZW96, Class 10 trip, 100 kA breaking capacity at 400 V, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"The rated voltage range spans 20 to 690 V, covering common low-voltage motor circuits from 24 V control transformers to 480/600 V line feeds. Breaking capacity is 100 kA at 240 V, 400 V, and 500 V, dropping to 2 kA at 690 V. On a 400 V line this holds the full fault current available from a typical 1 MVA transformer — no upstream fuse needed for short-circuit coordination in most panel designs. Any mounting position allowed. Dimensions: 45 mm wide, 90 mm tall, 75 mm deep. Clearance requirements: 20 mm above and below, 9 mm to the side, zero forward or backward clearance needed. Main circuit terminals are screw-type, accepting 2×(0.5 to 1.5 mm²) or 2×(0.75 to 2.5 mm²) solid or stranded copper. Torque to M3 screw size. No ground-fault detection — this is a motor-protection-only device, not a GFCI.","metaTitle":"Siemens 3RV1011-1CA10-ZW96 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-1CA10-ZW96 motor protection circuit breaker, Class 10 trip, 100 kA breaking capacity at 400 V. Available to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 35 A","at 500 V":"gL/gG 25 A","at 690 V":"gL/gG 25 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.17 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"2.5 A","at 500 V rated value":"100 kA","at 600 V rated value":"2.5 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 200/208 V rated value":"0.5 hp","at 220/230 V rated value":"0.5 hp","at 460/480 V rated value":"1 hp","at 575/600 V rated value":"1.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"10 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"2.5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"2.5 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"2.5 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"33 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.8 ... 2.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f78cf8c95a2a0f5b384d2541da5230e0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=178940&mlfb=3RV1011-1CA10-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1CA10-ZW96/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV1011-1CA10-ZW96 drop into a panel specified around 3RV1011-1AA15 without rewiring?","answer":"Both are SIRIUS motor protection breakers with the same 45 mm width, DIN rail mounting, and screw terminals. The -ZW96 variant carries a different factory-set rating or special code — verify the specific current setting on the nameplate matches your motor FLA before swapping. Physical fit is identical; electrical settings may differ."},{"question":"What is the breaking capacity at 400 V?","answer":"100 kA at 400 V. That covers most industrial service-entrance fault levels without requiring upstream current-limiting fuses."},{"question":"Where can I buy 3RV1011-1CA10-ZW96 and how is it quoted?","answer":"This part is sourced to order through independent distribution. Submit an RFQ with your quantity and target delivery date; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1CA10-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1CA10-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}