{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1CA10-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1CA10-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1CA10-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1CA10-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV1011-1CA10-ZW97, Trip Class 10, 100 kA interrupting capacity at 400 V, phase failure detection, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"## Motor protection circuit breaker — SIRIUS 3RV1011-1CA10-ZW97 Rated interrupting capacity reaches 100 kA at 240 V, 400 V, and 500 V, dropping to 2 kA at 690 V. At 400 V, the datasheet specifies a gL/gG 35 A backup fuse; at 500 V and 690 V, gL/gG 25 A. At 240 V, no backup fuse is required. These are the coordination limits — exceed them and the interrupting capacity of the device alone is what clears the fault. The 2 kA rating at 690 V is a hard ceiling; if the available fault current at 690 V exceeds that, a current-limiting upstream device is mandatory. The lifecycle stage for this order code is listed as current, meaning the manufacturer continues to produce it as a standard catalog item. No successor has been announced. ## Mounting clearances and wiring Clearance requirements per the datasheet: 20 mm upwards, 20 mm downwards, 9 mm at the side, 0 mm forwards, 0 mm backwards. These are the minimum free air spaces needed for heat dissipation and arc venting — not optional for maintaining the SCCR rating. Main circuit terminals accept 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²) solid or stranded, with M3 screw-type terminals. ## Environmental limits The rated voltage range is 20…690 V. Maximum switching frequency under AC-3 or AC-3e duty is 15 operations per hour.","metaTitle":"Siemens 3RV1011-1CA10-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-1CA10-ZW97 motor protection circuit breaker. Trip Class 10, 100 kA SCCR at 400 V. Phase failure detection. DIN rail mount. Current lifecycle stage. Quoted to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 35 A","at 500 V":"gL/gG 25 A","at 690 V":"gL/gG 25 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.17 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"2.5 A","at 500 V rated value":"100 kA","at 600 V rated value":"2.5 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 200/208 V rated value":"0.5 hp","at 220/230 V rated value":"0.5 hp","at 460/480 V rated value":"1 hp","at 575/600 V rated value":"1.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"10 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"2.5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"2.5 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"2.5 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"33 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.8 ... 2.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b6b219023b31c07638f430a331bbe29d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=144532&mlfb=3RV1011-1CA10-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1CA10-ZW97/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RV1011-1CA10-ZW97?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"Will 3RV1011-1CA10-ZW97 drop into a panel specified around 3RV1011-0HA10 without rewiring?","answer":"Both are SIRIUS 3RV10 motor protection circuit breakers with the same 45 mm width and 90 mm height, and both mount on 35 mm DIN rail. The -1CA10-ZW97 has a different thermal setting range and interrupting capacity than the -0HA10 variant, so verify the motor FLA and available fault current against the nameplate before assuming a drop-in swap. Terminal wiring (M3 screw-type, 2×0.5…2.5 mm²) is identical."},{"question":"What compliance documentation does Siemens provide for 3RV1011-1CA10-ZW97?","answer":"As a standard SIRIUS catalog item, the manufacturer provides a declaration of conformity to IEC/EN 60947-2 and 60947-4-1, along with RoHS and REACH compliance declarations. UL and CSA approvals are standard for the SIRIUS 3RV10 series. Specific cert numbers are available with the product documentation on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1CA10-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1CA10-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}