{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1DA10-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1DA10-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1DA10-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1DA10-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1DA10-ZW98 motor protection circuit breaker, Class 10, screw terminals, 45 mm wide, 75 mm deep, 100 kA breaking capacity at 400 V.","salesMarkdown":"## Motor protection circuit breaker, SIRIUS series — Class 10 trip curve The Class 10 trip characteristic means it will trip within 10 seconds at 7.2× the thermal setting — the standard for standard-duty motor starting where the acceleration time is under 10 seconds. The 45 mm width (three module spaces) and 75 mm depth fit standard distribution boards and motor control center buckets. Terminals are M3 screw-type, accepting 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded copper. ## Breaking capacity and fuse coordination For installations where the prospective fault current exceeds the breaker's interrupting rating at the operating voltage, the datasheet specifies upstream fusing: at 400 V, a gL/gG 40 A fuse is required; at 500 V and 690 V, a gL/gG 35 A fuse is required. At 240 V, no upstream fuse is required — the breaker is self-protecting at that voltage level. ## Environmental limits and storage","metaTitle":"Siemens 3RV1011-1DA10-ZW98 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-1DA10-ZW98 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA breaking at 400 V, screw terminals, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 40 A","at 500 V":"gL/gG 35 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.25 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"3.2 A","at 500 V rated value":"3 kA","at 600 V rated value":"3.2 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.1 hp","at 200/208 V rated value":"0.5 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"2 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"3.2 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"3.2 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"3.2 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"42 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.2 ... 3.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=90324&mlfb=3RV1011-1DA10-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1DA10-ZW98/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-1DA10-ZW98?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3RV1011-1DA10-ZW98 at 400 V?","answer":"100 kA at 400 V. At 690 V the rating is 2 kA."},{"question":"Does 3RV1011-1DA10-ZW98 include phase failure detection?","answer":"Yes, phase failure detection is built in. Ground fault detection is not included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1DA10-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1DA10-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}