{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1DA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1DA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1DA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1DA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-1DA10-ZX95, Class 10 trip, 100 kA breaking capacity at 400 V, phase failure detection, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"It combines overload protection (Class 10 trip curve) with short-circuit interruption, rated for 100 kA breaking capacity at both 240 V and 400 V. No ground fault detection on this variant. That is the standard for standard-duty motor starting — not for high-inertia loads like crushers or centrifuges, which need Class 20 or 30. For a pump, fan, compressor, or conveyor drive, Class 10 is what the motor winding insulation expects. That is the standard DIN-rail profile found in every industrial control panel. Mounting position is any orientation. Clearance requirements: 20 mm upward, 20 mm downward, 9 mm to the side, zero forward or backward. That 9 mm side gap is tight — adjacent devices must respect it, or the arc-chamber venting and conductor bending space is compromised. ## Breaking capacity and short-circuit coordination For most 400 V industrial distribution (where prospective fault current is typically 25–65 kA), the 100 kA figure gives plenty of SCCR headroom. The required backup fuse varies by voltage: at 240 V none required; at 400 V use gL/gG 40 A; at 500 V or 690 V use gL/gG 35 A. Main current circuit terminals are screw-type, size M3. Accepts two conductors per terminal: 2 × (0.5 to 1.5 mm²) solid or stranded, or 2 × (0.75 to 2.5 mm²). That is standard for motor branch circuits up to the rated current of this frame.","metaTitle":"Siemens 3RV1011-1DA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-1DA10-ZX95 SIRIUS motor protection circuit breaker. Class 10 trip, 100 kA breaking capacity at 400 V, phase failure detection. DIN rail mount. Current lifecycle. So","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 40 A","at 500 V":"gL/gG 35 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.25 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"3.2 A","at 500 V rated value":"3 kA","at 600 V rated value":"3.2 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at 110/120 V rated value":"0.1 hp","at 200/208 V rated value":"0.5 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"2 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"3.2 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"3.2 A","Design Of The Short-Circuit Trip":"magnetic","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Switching Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"42 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.2 ... 3.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=229609&mlfb=3RV1011-1DA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1DA10-ZX95/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for the 3RV1011-1DA10-ZX95?","answer":"Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time through independent distribution channels. This is a current-production part, not surplus or obsolete."},{"question":"Will the 3RV1011-1DA10-ZX95 drop into a panel specified for the 3RV1011-1HA10?","answer":"Both are SIRIUS 45 mm wide motor protection circuit breakers on the same DIN-rail footprint, so the mechanical fit is identical. The difference is in the internal trip settings and accessory compatibility — verify the overload range and any connected auxiliaries before swapping. No rewiring of the main power terminals is required."},{"question":"What compliance documentation does Siemens provide for this part?","answer":"As a SIRIUS product, the 3RV1011-1DA10-ZX95 carries the standard Siemens declarations of conformity for the Low Voltage Directive and relevant harmonized standards. RoHS and REACH compliance declarations are available from Siemens documentation. Specific certification marks (UL, CSA, CE) are listed on the product nameplate and in the manufacturer's certificate database."},{"question":"What is the depth of the 3RV1011-1DA10-ZX95?","answer":"The depth is 75 mm from the DIN-rail mounting surface to the front of the device. This is the dimension that matters for enclosure depth clearance behind the panel door."},{"question":"What is the width of the 3RV1011-1DA10-ZX95?","answer":"The width is 45 mm — a standard single-module width on 35 mm DIN rail. This determines how many units fit across a given panel width."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1DA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1DA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}