{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1EA10-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1EA10-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1EA10-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1EA10-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-1EA10-ZW98, Class 10 trip, 100 kA breaking capacity at 400 V, phase failure detection, screw and snap-on 35 mm DIN rail mounting.","salesMarkdown":"Rated for a voltage range of 20 to 690 V, it delivers a 100 kA breaking capacity at both 240 V and 400 V — that is the maximum fault current it can safely interrupt without welding its contacts or rupturing the housing. No ground fault detection on this variant — that is the ZW98 suffix's story: a special version without the ground-fault module. Clearance requirements: 20 mm upwards and downwards, 9 mm at the sides, zero forwards or backwards. That 9 mm side gap is tight — adjacent devices can sit nearly flush, but you still need room for the screwdriver on the M3 main contact terminals. Terminals accept 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded wire — typical for control circuit connections. The screw-type terminals are rated for the main current circuit.","metaTitle":"Siemens 3RV1011-1EA10-ZW98 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-1EA10-ZW98 motor protection circuit breaker. Class 10 trip, 100 kA breaking capacity at 400 V, phase failure detection. Current lifecycle stage. Quoted to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 40 A","at 500 V":"gL/gG 35 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.33 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"4 A","at 500 V rated value":"3 kA","at 600 V rated value":"4 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.13 hp","at 200/208 V rated value":"0.8 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"3 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"4 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"4 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"4 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"52 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.8 ... 4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=178917&mlfb=3RV1011-1EA10-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1EA10-ZW98/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV1011-1EA10-ZW98 drop into a panel specified around 3RV1011-1HA10 without rewiring?","answer":"Both are 45 mm wide SIRIUS motor protection breakers on the same DIN rail footprint, so the mechanical fit is identical. The difference is in the internal protection settings and the ZW98 suffix (no ground fault module on this variant). Check the thermal setting range on your 1HA10 against this unit's range before swapping — the trip curve and terminal layout are the same Class 10 design."},{"question":"What compliance documentation does this brand provide for 3RV1011-1EA10-ZW98?","answer":"Siemens SIRIUS products typically carry UL, CSA, CE, and IEC certifications. Specific documentation (RoHS, REACH, UL file number) is available on request at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1EA10-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1EA10-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}