{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1EA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1EA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1EA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1EA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-1EA10-ZX95, Trip Class 10, screw-type terminals, 100 kA SCCR at 400 V, 45 mm wide, DIN rail mount.","salesMarkdown":"It mounts on 35 mm DIN rail per DIN EN 60715 via screw or snap-on fastening, and accepts 2x (0.5–1.5 mm²) or 2x (0.75–2.5 mm²) solid or stranded conductors on the main contacts (M3 screws). Trip Class 10 means the thermal overload element trips within 10 seconds at 7.2× the rated current — standard for standard-duty motor starting where the acceleration time stays under 10 seconds. No ground-fault detection on this variant. Mounting position is any orientation. Required clearances: 20 mm upwards, 20 mm downwards, 9 mm at the side, 0 mm forwards, 0 mm backwards. The zero forward/backward clearance means it can sit flush against a panel door or backplate without derating — useful when packing multiple breakers into a shallow enclosure.","metaTitle":"Siemens 3RV1011-1EA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-1EA10-ZX95 SIRIUS motor protection circuit breaker, Trip Class 10, 100 kA SCCR at 400 V, screw terminals, DIN rail mount. Active production. Sourced to order agains","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 40 A","at 500 V":"gL/gG 35 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.33 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"4 A","at 500 V rated value":"3 kA","at 600 V rated value":"4 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.13 hp","at 200/208 V rated value":"0.8 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"3 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"4 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"4 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"4 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"52 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.8 ... 4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/58ea26e7c88ff629562835dc68d3bd02.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=450432&mlfb=3RV1011-1EA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1EA10-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-1EA10-ZX95 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 3RV1011-1EA10-ZX95 drop into a panel that was specified around 3RV1011-1HA10 without rewiring?","answer":"Both are SIRIUS motor protection circuit breakers in the same 45 mm width and DIN-rail footprint, so the physical swap is straightforward — same screw-type terminals and M3 main contact screws. Verify the trip class and current range of the 1HA10 variant against the load before substituting; the 1EA10 is Trip Class 10."},{"question":"What compliance documentation does this brand provide for 3RV1011-1EA10-ZX95?","answer":"As a SIRIUS product, it carries the standard Siemens declarations for RoHS, REACH, and CE marking. UL and CSA approvals are typical for this series, but confirm the specific certification markings on the nameplate or the manufacturer's declaration for the exact order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1EA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1EA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}