{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1FA10-0FJ0-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1FA10-0FJ0-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1FA10-0FJ0-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1FA10-0FJ0-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1FA10-0FJ0-ZX95 motor protection circuit breaker, 5 A continuous current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, phase failure detection, screw-type terminals, DIN-rail mount.","salesMarkdown":"It carries a continuous current rating of 5 A and a CLASS 10 trip class, meaning it will disconnect within 10 seconds at 7.2× the set current — fast enough to protect standard induction motors during a stall or locked-rotor event. The breaker offers a 100 kA breaking capacity at 400 V AC, which safely interrupts high fault currents without cascading upstream, and also delivers 100 kA at 240 V, 3 kA at 500 V, and 2 kA at 690 V. The 45 mm width (3 TE) fits standard panel slots, and the 81 mm depth leaves clearance for wiring behind the rail. Terminal connections accept solid or stranded conductors: 2× (0.5…1.5 mm²) and 2× (0.75…2.5 mm²) per pole, with screw-type terminals on the main circuit.","metaTitle":"Siemens 3RV1011-1FA10-0FJ0-ZX95 SIRIUS Motor Protection Circ","metaDescription":"Siemens 3RV1011-1FA10-0FJ0-ZX95 SIRIUS motor protection circuit breaker, 5 A continuous current, CLASS 10 trip, 100 kA breaking at 400 V, phase failure detection, DIN-rail mount. C","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","Maximum":"2 000 m","Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Backwards":"0 mm","Trip class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","On The Front":"IP20","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","Auxiliary switch":"Yes","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Shock resistance":"25g / 11 ms","Mounting position":"any","Product brand name":"SIRIUS","Product designation":"circuit breaker","at 400 V rated value":"1.5 kW","Design of the product":"for motor protection","For Auxiliary Contacts":"0","Ground fault detection":"No","Phase failure detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","Continuous current rated value":"5 A","at AWG conductors for main contacts":"2x (18 ... 14)","Surge voltage resistance rated value":"6 000 V","at AC in hot operating state per pole":"2.4 W","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","For Auxiliary And Control Current Circuit":"screw-type terminals","Removable Terminal For Auxiliary And Control Circuit":"No","Design of the overcurrent release and short-circuit release":"thermomagnetic","Arrangement of electrical connectors for main current circuit":"front side","Adjustable pick-up value current of the current-dependent overload release":"3.5 ... 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=498744&mlfb=3RV1011-1FA10-0FJ0-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1FA10-0FJ0-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-1FA10-0FJ0-ZX95 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional second-source for 3RV1011-1FA10-0FJ0-ZX95?","answer":"The 3RV1011-1HA10 is a close peer in the same SIRIUS family, but verify the continuous current rating and trip class match your motor nameplate before substituting — the 3RV1011-1FA10-0FJ0-ZX95 is a 5 A CLASS 10 device with phase failure detection."},{"question":"Will 3RV1011-1FA10-0FJ0-ZX95 drop into a panel specified around 3RV1011-1HA10 without rewiring?","answer":"Both share the same 45 mm width, 35 mm DIN-rail mount, and screw-type terminal footprint, so mechanical fit is identical. However, always confirm the current rating and trip class match your motor protection requirements before swapping."},{"question":"What compliance documentation does this brand provide for 3RV1011-1FA10-0FJ0-ZX95?","answer":"Siemens SIRIUS products typically carry CE, UL, CSA, and CCC certifications, and are RoHS and REACH compliant. Specific documentation is available upon request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1FA10-0FJ0-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1FA10-0FJ0-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}