{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1FA10-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1FA10-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1FA10-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1FA10-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV1011-1FA10-ZW97, Class 10, 100 kA breaking capacity at 400 V, screw terminals, 45 mm width.","salesMarkdown":"Breaking capacity hits 100 kA at both 240 V and 400 V, so it can interrupt high fault currents without cascading upstream. The 45 mm width (three module spaces) keeps panel density reasonable for a motor branch. Screw-type terminals on the main circuit accept 2x (0.5 to 2.5 mm²) solid or stranded. No ground fault detection — that's separate if the application needs it.","metaTitle":"Siemens 3RV1011-1FA10-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-1FA10-ZW97 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA breaking capacity at 400 V. Screw terminals, phase failure detection. Sourced to order. Re","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 50 A","at 500 V":"gL/gG 35 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"5 A","at 500 V rated value":"3 kA","at 600 V rated value":"5 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.17 hp","at 200/208 V rated value":"1 hp","at 220/230 V rated value":"1 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"3 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"5 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"5 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"65 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"3.5 ... 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/89b2785bd8aef5520ae47fa0a214fa97.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=533223&mlfb=3RV1011-1FA10-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1FA10-ZW97/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV1011-1FA10-ZW97 drop into a panel specified for 3RV1011-1HA10?","answer":"Both are 45 mm wide SIRIUS motor protection breakers with the same DIN rail footprint and terminal layout, so mechanical fit is identical. The difference is in the internal settings and special version coding — check the trip curve and auxiliary options before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1FA10-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1FA10-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}