{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1FA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1FA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1FA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1FA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1FA10-ZX95 motor protection circuit breaker, Trip Class 10, 100 kA SCCR at 400 V, phase failure detection, screw-type terminals, 45 x 90 x 75 mm.","salesMarkdown":"## Motor protection circuit breaker for 45 mm DIN-rail panels It occupies a 45 mm width, 90 mm height, and 75 mm depth — a standard footprint that fits existing SIRIUS panel layouts without re-drilling. ## Mounting and terminal details Main circuit terminals are M3 screw-type, accepting 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²) solid or stranded copper. Required clearance above and below the unit is 20 mm; 9 mm at the sides; zero forward or backward clearance needed. For fault-current back-up, at 240 V no upstream fuse is required. At 400 V a gL/gG 50 A fuse is needed; at 500 V and 690 V a gL/gG 35 A fuse is specified.","metaTitle":"Siemens 3RV1011-1FA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-1FA10-ZX95 motor protection circuit breaker. Trip Class 10, 100 kA SCCR at 400 V, phase failure detection. DIN rail mount. Active production. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 50 A","at 500 V":"gL/gG 35 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"5 A","at 500 V rated value":"3 kA","at 600 V rated value":"5 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.17 hp","at 200/208 V rated value":"1 hp","at 220/230 V rated value":"1 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"3 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"5 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"5 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"65 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"3.5 ... 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ac0e9624eea0476231eba8afd4f618c4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=517225&mlfb=3RV1011-1FA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1FA10-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of this breaker at 400 V?","answer":"100 kA at 400 V."},{"question":"Will 3RV1011-1FA10-ZX95 drop into a panel specified around 3RV1011-1HA10 without rewiring?","answer":"Both share the same 45 mm width, 90 mm height, 75 mm depth, and DIN-rail mounting, so the footprint is identical. The terminal specs are also M3 screw-type, so no rewiring is needed for the main circuit. The key difference is the ZX95 variant includes a special customer-specific setting (the -ZX95 suffix), which may affect the thermal trip curve — verify the exact setting against the 1HA10's standard curve before swapping."},{"question":"Where can I buy 3RV1011-1FA10-ZX95?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ to get a firm commitment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1FA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1FA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}