{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1GA10-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1GA10-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1GA10-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1GA10-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1GA10-ZW97 motor protection circuit breaker, Class 10 trip, 6.3 A at 480/600 V, 100 kA breaking capacity at 400 V, screw and snap-on DIN rail mounting.","salesMarkdown":"## Motor protection circuit breaker for 480/600 V lines Rated 6.3 A at both 480 V and 600 V, it covers fractional to small-horsepower motors — the 230 V rating maps to 0.5 hp, 200/208 V to 1 hp, and 220/230 V to 1.5 hp. Breaking capacity hits 100 kA at 240 V and 400 V, dropping to 3 kA at 500 V and 2 kA at 690 V — the 100 kA figure means it can interrupt a bolted fault on a high-capacity transformer without upstream fuses needing to clear first. ## DIN rail fit and wiring Dimensions are 45 mm wide, 90 mm high, 75 mm deep — the 45 mm width occupies two standard 22.5 mm module spaces on the rail. Clearance requirements: 20 mm upwards and downwards, 9 mm to the side, zero forwards and backwards — tight panel layouts can push against those limits. Main circuit terminals are screw-type, accepting 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded copper; the main contact screws are M3. ## Coordination and selectivity notes For backup protection, the required upstream fuse changes with voltage: none needed at 240 V, gL/gG 50 A at 400 V, gL/gG 40 A at both 500 V and 690 V — a detail that matters when coordinating a panel with mixed voltage levels. Maximum operating frequency in AC-3 duty is 15 operations per hour — fine for a pump or fan cycling a few times an hour, not for a rapid-reversing conveyor. Rated operational voltage spans 20 to 690 V, covering most low-voltage motor control schemes worldwide.","metaTitle":"Siemens 3RV1011-1GA10-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-1GA10-ZW97 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA SCCR at 400 V, 6.3 A at 480/600 V. Phase failure detection. Current lifecycle. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"gL/gG 50 A","at 500 V":"gL/gG 40 A","at 690 V":"gL/gG 40 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"6.3 A","at 500 V rated value":"3 kA","at 600 V rated value":"6.3 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.25 hp","at 200/208 V rated value":"1 hp","at 220/230 V rated value":"1.5 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"6.3 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"6.3 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"6.3 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"82 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"4.5 ... 6.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=48559&mlfb=3RV1011-1GA10-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1GA10-ZW97/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to 3RV1011-1GA10-ZW97?","answer":"The 3RV1011-1HA10 is a close sibling in the same SIRIUS family — same Class 10 trip, same 45 mm width, same DIN rail mount — but verify the current rating and fuse coordination for your specific voltage before substituting."},{"question":"Will 3RV1011-1GA10-ZW97 drop into a panel specified for 3RV1011-1HA10?","answer":"The 45 mm width, 90 mm height, and 75 mm depth are identical across the 3RV1011 family, and both use screw and snap-on DIN rail mounting — mechanical fit is the same, but check the current rating and fuse requirements at your line voltage."},{"question":"How do I get current pricing and availability for 3RV1011-1GA10-ZW97?","answer":"Sourced and quoted to order against an RFQ through independent distribution — availability and current pricing are confirmed at quote time, no stock or price figures are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1GA10-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1GA10-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}