{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1GA25","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1GA25","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1GA25","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1GA25","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor-protective circuit breaker, 3RV1011-1GA25, 6.3 A continuous current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, spring-loaded terminals, screw and snap-on DIN rail mounting.","salesMarkdown":"The Siemens 3RV1011-1GA25 is a SIRIUS motor-protective circuit breaker rated for 6.3 A continuous current with a CLASS 10 trip curve — meaning it trips within 10 seconds at 7.2× the set current, fast enough to protect standard induction motors from locked-rotor damage without nuisance tripping on normal starts. ## Breaking capacity and fault clearing Rated breaking capacity hits 100 kA at 240 V AC and 400 V AC, dropping to 3 kA at 500 V AC and 2 kA at 690 V AC. ## Termination and mounting Spring-loaded terminals on the main circuit accept 2x (0.25... 2.5 mm²) solid or 2x (24... 14 AWG) stranded — no screw torque to check, just strip and push. Shock rated at 25 g / 11 ms, so it holds up in transport and moderate vibration environments.","metaTitle":"Siemens 3RV1011-1GA25 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV1011-1GA25 SIRIUS motor-protective circuit breaker, 6.3 A continuous current, CLASS 10 trip, 100 kA breaking capacity at 400 V. Spring-loaded terminals, DIN rail mount.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","Maximum":"2 000 m","at 24 V":"1 A","at 60 V":"0.15 A","at 230 V":"0.5 A","Backwards":"0 mm","Trip class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","On The Front":"IP20","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","Auxiliary switch":"Yes","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Shock resistance":"25g / 11 ms","Mounting position":"any","Product brand name":"SIRIUS","Product designation":"circuit breaker","at 400 V rated value":"2.2 kW","Design of the product":"for motor protection","For Auxiliary Contacts":"0","Ground fault detection":"No","Phase failure detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","Continuous current rated value":"6.3 A","Design of the auxiliary switch":"transverse","at AWG conductors for main contacts":"2x (24 ... 14)","Surge voltage resistance rated value":"6 000 V","at AC in hot operating state per pole":"2.4 W","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Removable Terminal For Auxiliary And Control Circuit":"No","Design of the overcurrent release and short-circuit release":"thermomagnetic","Arrangement of electrical connectors for main current circuit":"front side","Adjustable pick-up value current of the current-dependent overload release":"4.5 ... 6.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=208344&mlfb=3RV1011-1GA25","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1GA25/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV1011-1GA25 drop into a panel specified around 3RV1011-1AA15 without rewiring?","answer":"Both are 45 mm wide SIRIUS motor-protective breakers with the same DIN rail footprint and spring-loaded terminals, so mechanical fit and wiring are identical. The key difference is the current rating: the 1GA25 is set at 6.3 A continuous, while the 1AA15 is rated lower — verify the motor FLA matches the breaker's setting range before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1GA25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1GA25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}