{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1HA10-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1HA10-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1HA10-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1HA10-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-1HA10-ZW96, Class 10 trip, 45 mm wide, screw-type terminals, phase failure detection, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"## Motor protection circuit breaker, Class 10 trip The Siemens 3RV1011-1HA10-ZW96 is a SIRIUS motor protection circuit breaker designed for motor protection, with a Class 10 trip characteristic that clears overloads within 10 seconds at 7.2× the thermal setting — matching the thermal time constant of standard induction motors during a stall or jam. It mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, occupying 45 mm width, 90 mm height, and 75 mm depth — a standard three-module footprint that fits existing panel layouts without re-spacing. ## Breaking capacity and backup fuse coordination Rated breaking capacity reaches 100 kA at 240 V, dropping to 13 kA at 400 V, 3 kA at 500 V, and 2 kA at 690 V — the 400 V figure is the one that governs on a standard 400 V three-phase line, and it comfortably exceeds typical 10 kA SCCR requirements for motor branch circuits. For higher fault currents, the manufacturer specifies backup fuse coordination: gL/gG 80 A at 240 V, 63 A at 400 V, 40 A at 500 V, and 40 A at 690 V — these are the maximum fuse ratings that still allow the breaker to clear a fault without damage to itself. ## Termination and environmental limits Main circuit connections use screw-type terminals accepting 2× (0.5…1.5 mm²) or 2× (0.75…2.5 mm²) solid or stranded copper — M3 screws on the main contacts, so a PZ1 bit and the standard torque spec apply.","metaTitle":"Siemens 3RV1011-1HA10-ZW96 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-1HA10-ZW96 SIRIUS motor protection circuit breaker, Class 10 trip, 45 mm wide, screw terminals, phase failure detection. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"gL/gG 80 A","at 400 V":"gL/gG 63 A","at 500 V":"gL/gG 40 A","at 690 V":"gL/gG 40 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"1 hp","at 240 V rated value":"100 kA","at 400 V rated value":"13 kA","at 480 V rated value":"8 A","at 500 V rated value":"3 kA","at 600 V rated value":"8 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.33 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"2 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"8 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"8 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"8 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"104 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"5.5 ... 8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/731bda8d5c875aaf0d3a72211ea473e0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=91719&mlfb=3RV1011-1HA10-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1HA10-ZW96/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RV1011-1HA10-ZW96?","answer":"Submit an RFQ through this listing; the part is sourced to order, and current pricing and availability are confirmed at quote time."},{"question":"Will 3RV1011-1HA10-ZW96 drop into a panel that was specified around 3RV1011-1HA10 without rewiring?","answer":"The 3RV1011-1HA10-ZW96 shares the same 45 mm width, 90 mm height, 75 mm depth, and screw-type terminal layout as the base 3RV1011-1HA10, so it fits the same DIN rail footprint and wiring scheme."},{"question":"What is 3RV1011-1HA10-ZW96's listed depth?","answer":"The depth is 75 mm, which is standard for this SIRIUS frame size."},{"question":"What is 3RV1011-1HA10-ZW96's listed width?","answer":"The width is 45 mm, occupying three standard 15 mm DIN-rail module positions."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1HA10-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1HA10-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}