{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1HA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1HA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1HA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1HA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-1HA10-ZX95, CLASS 10 trip, 45 mm wide, screw and snap-on DIN rail mount.","salesMarkdown":"At 45 mm wide and 90 mm tall, it occupies a single standard modular slot, leaving room alongside contactors and overload relays in a dense panel layout. At 690 V it still clears 2 kA, enough for many 690 V motor circuits in mining or marine gear. That prevents single-phasing damage on a motor that would otherwise try to run on two phases and burn up the winding. The gL/gG fuse backup ratings let you coordinate with upstream fuses: 80 A at 240 V, 63 A at 400 V, 40 A at 500 V and 690 V. That tells your panel designer what fuse size to spec ahead of this breaker to keep selective coordination. Mounting position is any — vertical, horizontal, upside down — no derating needed for orientation. Screw-type terminals on the main circuit accept 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded copper. Terminal screws are M3. Clearance around the unit: 20 mm above and below, 9 mm to the side, zero in front or back — tight panel spacing works. ## Environmental range and storage Operates from -20 °C to +60 °C, with temperature compensation active across that entire span so the thermal trip curve stays accurate. Rated voltage range covers 20 V to 690 V, so it works on control voltages as low as 24 VAC/DC as well as standard 400 V and 690 V power circuits.","metaTitle":"Siemens 3RV1011-1HA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-1HA10-ZX95 motor protection circuit breaker. CLASS 10 trip, 100 kA at 240 V, phase failure detection. 45 mm wide, DIN rail mount. Sourced to order — request","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"gL/gG 80 A","at 400 V":"gL/gG 63 A","at 500 V":"gL/gG 40 A","at 690 V":"gL/gG 40 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"1 hp","at 240 V rated value":"100 kA","at 400 V rated value":"13 kA","at 480 V rated value":"8 A","at 500 V rated value":"3 kA","at 600 V rated value":"8 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at 110/120 V rated value":"0.33 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"2 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"8 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"8 A","Design Of The Short-Circuit Trip":"magnetic","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Switching Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"104 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"5.5 ... 8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ffb96deee0a95cdfb543bf730ddf6e67.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=144824&mlfb=3RV1011-1HA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1HA10-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV1011-1HA10-ZX95 drop into a panel specified around 3RV1011-1HA10 without rewiring?","answer":"Yes — same 45 mm width, same screw and snap-on DIN rail mount, same terminal specs. The -ZX95 suffix indicates a special version but the mechanical footprint is identical."},{"question":"What is the short-circuit breaking capacity at 400 V?","answer":"13 kA at 400 V, with a gL/gG fuse backup rating of 63 A at that voltage level."},{"question":"Where can I buy 3RV1011-1HA10-ZX95 and get current pricing?","answer":"Sourced to order through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1HA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1HA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}