{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1JA10-0FJ0-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1JA10-0FJ0-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1JA10-0FJ0-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JA10-0FJ0-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-1JA10-0FJ0-ZX95, 10 A continuous rated current, CLASS 10 trip class, 50 kA breaking capacity at 400 V AC, screw-type terminals, IP20 front.","salesMarkdown":"## Breaking capacity and fault clearing This breaker clears 100 kA at 240 V AC, 50 kA at 400 V AC, 3 kA at 500 V AC, and 2 kA at 690 V AC. The surge voltage resistance rating of 6 000 V ensures the internal gap withstands switching transients on inductive motor circuits. The 45 mm width and 90 mm height fit standard motor starter assemblies in a control panel. Terminal capacity accepts 2× (0.5 to 1.5 mm²) solid or stranded, or 2× (0.75 to 2.5 mm²) — sized for the motor leads this breaker typically protects.","metaTitle":"Siemens 3RV1011-1JA10-0FJ0-ZX95 SIRIUS Motor Protection Circ","metaDescription":"Siemens SIRIUS 3RV1011-1JA10-0FJ0-ZX95 motor protection circuit breaker, 10 A continuous, CLASS 10 trip, 50 kA at 400 V. Current lifecycle. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","Maximum":"2 000 m","Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Backwards":"0 mm","Trip class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","On The Front":"IP20","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","Auxiliary switch":"Yes","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Shock resistance":"25g / 11 ms","Mounting position":"any","Product brand name":"SIRIUS","Product designation":"circuit breaker","at 400 V rated value":"4 kW","Design of the product":"for motor protection","For Auxiliary Contacts":"0","Ground fault detection":"No","Phase failure detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","Continuous current rated value":"10 A","at AWG conductors for main contacts":"2x (18 ... 14)","Surge voltage resistance rated value":"6 000 V","at AC in hot operating state per pole":"3.1 W","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","For Auxiliary And Control Current Circuit":"screw-type terminals","Removable Terminal For Auxiliary And Control Circuit":"No","Design of the overcurrent release and short-circuit release":"thermomagnetic","Arrangement of electrical connectors for main current circuit":"front side","Adjustable pick-up value current of the current-dependent overload release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=75812&mlfb=3RV1011-1JA10-0FJ0-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JA10-0FJ0-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RV1011-1JA10-0FJ0-ZX95?","answer":"The closest functional peer is the 3RV1011-1HA10. Both are SIRIUS motor protection circuit breakers with the same 45 mm width, CLASS 10 trip, and screw-type terminals. The key difference is the continuous current rating: the -1JA10-0FJ0-ZX95 is rated 10 A, while the -1HA10 is rated at a different current level. Verify the motor FLA before substituting."},{"question":"What is the depth of 3RV1011-1JA10-0FJ0-ZX95?","answer":"The depth is 81 mm, which is the dimension from the DIN rail mounting surface to the front of the breaker body."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1JA10-0FJ0-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1JA10-0FJ0-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}