{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1JA10-ZI45","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1JA10-ZI45","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1JA10-ZI45","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JA10-ZI45","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1JA10-ZI45, motor protection circuit breaker, size S00, CLASS 10, adjustable overload release 7-10 A, instantaneous short-circuit trip 130 A, screw terminals, snap-on DIN rail mounting.","salesMarkdown":"The adjustable overload release spans 7 to 10 A, letting you dial in the exact motor FLA without swapping the breaker. The magnetic short-circuit release is fixed at 130 A, so it clears a bolted fault fast while ignoring the motor's starting transient. At 400 V the unit is rated for 4 000 W of motor output. The S00 frame is the smallest SIRIUS footprint, so it fits tightly alongside contactors and relays in a crowded enclosure. Mounting position is unrestricted, which simplifies layout in vertical or horizontal bus runs. The power loss at rated current is 9.25 W total, 3.1 W per pole in hot operating state — modest enough that adjacent devices don't need extra derating in a standard IP20 cabinet.","metaTitle":"Siemens 3RV1011-1JA10-ZI45 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-1JA10-ZI45 motor protection circuit breaker, size S00, CLASS 10, adjustable overload 7-10 A, screw terminals, DIN rail mount. Current lifecycle, available to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Trip class":"CLASS 10","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","lifecycle_stage":"current","Mounting position":"any","Product brand name":"SIRIUS","Product designation":"Circuit breaker","at 400 V rated value":"4 000 W","Design of the product":"For motor protection","For Main Current Circuit":"screw-type terminals","Size of the circuit-breaker":"S00","at AC in hot operating state":"9.25 W","Operating current rated value":"10 A","at AC in hot operating state per pole":"3.1 W","Arrangement of electrical connectors for main current circuit":"Top and bottom","Adjustable pick-up value current of the current-dependent overload release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=809370&mlfb=3RV1011-1JA10-ZI45","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JA10-ZI45/alternatives.json"},"ai":{"faq":[{"question":"What is the adjustable overload range on this breaker?","answer":"The current-dependent overload release adjusts from 7 to 10 A, letting you match the motor nameplate FLA precisely."},{"question":"Does 3RV1011-1JA10-ZI45 mount on standard DIN rail?","answer":"Yes, screw and snap-on mounting onto 35 mm standard mounting rail per DIN EN 60715. Mounting position is any orientation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1JA10-ZI45","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1JA10-ZI45 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}