{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1JA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1JA15","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1JA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV1011-1JA15, CLASS 10 trip, 100 kA at 240 V, screw and snap-on 35 mm DIN rail mount.","salesMarkdown":"The Siemens SIRIUS 3RV1011-1JA15 is a motor-protective circuit breaker rated for CLASS 10 trip — meaning it disconnects within 10 seconds at 7.2× the thermal setting, which is the standard for standard-duty induction motors (pumps, fans, compressors) that don't need the faster CLASS 5 or the slower CLASS 20. At 400 V it drops to 13 kA, at 500 V to 3 kA, and at 690 V to 2 kA. The evidence also lists required backup fuse ratings (gL/gG) at each voltage level: 80 A at 240 V, 63 A at 400 V, 50 A at 500 V and 690 V. If you're coordinating with upstream fuses, those are the numbers to use. ## Motor current and auxiliary contacts For motor loads, the breaker carries 1.5 hp at 230 V, and 10 A at both 480 V and 600 V — that maps to a small motor, roughly 5–7.5 hp depending on voltage. The auxiliary contact block is rated 1 A at 24 V, 2 A at 110–125 V, 0.5 A at 230 V, and 0.15 A at 60 V. Those are the switching ratings for the signal side, not the main power path. ## Environmental and wiring The terminals accept solid or stranded wire: 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²).","metaTitle":"Siemens 3RV1011-1JA15 SIRIUS Circuit Breaker, 100 kA at 240","metaDescription":"Siemens 3RV1011-1JA15 SIRIUS motor-protective circuit breaker. CLASS 10 trip, 100 kA breaking capacity at 240 V. Screw and snap-on 35 mm DIN rail. Sourced to order — RFQ for availa","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Note":"1","Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 110 V":"2 A","at 120 V":"2 A","at 125 V":"2 A","at 230 V":"0.5 A","at 240 V":"gL/gG 80 A","at 400 V":"gL/gG 63 A","at 500 V":"gL/gG 50 A","at 690 V":"gL/gG 50 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"1.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"13 kA","at 480 V rated value":"10 A","at 500 V rated value":"3 kA","at 600 V rated value":"10 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"7.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"10 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"10 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"10 A","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"3.1 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"130 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f0f9de3c3f809de4376773822642cd4d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=88102&mlfb=3RV1011-1JA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JA15/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3RV1011-1JA15?","answer":"The 3RV1011-1HA10 is a close peer in the same SIRIUS family — same mounting footprint and CLASS 10 trip, but check the specific current and breaking capacity ratings for your application."},{"question":"What is the breaking capacity of 3RV1011-1JA15 at 240 V?","answer":"100 kA at 240 V, with a required backup fuse of gL/gG 80 A."},{"question":"Where can I buy 3RV1011-1JA15?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution — submit an RFQ for current availability and pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1JA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1JA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}