{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1JA25","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1JA25","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1JA25","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JA25","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1JA25 motor protection circuit breaker, 10 A continuous rated current, CLASS 10 trip class, 50 kA breaking capacity at 400 V AC, spring-loaded terminals, screw and snap-on 35 mm DIN rail mounting.","salesMarkdown":"## Motor protection circuit breaker for panel integration Rated breaking capacity reaches 50 kA at 400 V AC, sufficient for most industrial distribution panels with high fault-current potential; at 240 V AC it handles 100 kA, and at 690 V AC it still interrupts 2 kA. The 45 mm wide housing mounts via screw or snap-on onto 35 mm standard mounting rail per DIN EN 50022, fitting a standard panel footprint with 81 mm depth and 90 mm height. Spring-loaded terminals on both the main current circuit and the auxiliary/control circuit accept 2x (0.25... 2.5 mm²) solid or stranded wire (24–14 AWG), reducing wiring time compared to screw-clamp alternatives. Shock resistance rated at 25g / 11 ms, suitable for installation on machinery with moderate vibration. Substance prohibitance date of 01.01.2013 indicates RoHS compliance from that date forward. Surge voltage resistance rated at 6,000 V, confirming overvoltage category III coordination for industrial control panels.","metaTitle":"Siemens 3RV1011-1JA25 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV1011-1JA25 SIRIUS motor protection circuit breaker, 10 A continuous, CLASS 10 trip, 50 kA at 400 V. Spring-loaded terminals, phase failure detection. Current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","at 24 V":"1 A","at 60 V":"0.15 A","at 230 V":"0.5 A","Backwards":"0 mm","Trip Class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"4 kW","Design Of The Product":"for motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"9.25 W","Substance Prohibitance (Date)":"01.01.2013","Continuous Current Rated Value":"10 A","Design Of The Auxiliary Switch":"transverse","at AWG cables for main contacts":"2x (24 ... 14)","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"spring-loaded terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AWG cables for auxiliary contacts":"2x (24 ... 14)","at AC in hot operating state per pole":"3.1 W","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","number of CO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"10 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"thermomagnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"100 000","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=69276&mlfb=3RV1011-1JA25","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JA25/alternatives.json"},"ai":{"faq":[{"question":"What wire sizes does the spring-loaded terminal accept?","answer":"The spring-loaded terminals accept 2x (0.25... 2.5 mm²) solid or stranded wire, equivalent to 2x (24... 14 AWG)."},{"question":"Does 3RV1011-1JA25 include phase failure detection?","answer":"Yes, phase failure detection is built in, protecting the motor from single-phasing damage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1JA25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1JA25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}