{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1JK10-0AA1","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1JK10-0AA1","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1JK10-0AA1","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JK10-0AA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-1JK10-0AA1 circuit breaker, 10 A continuous current, 4 kW motor rating at 400 V AC, 50 kA breaking capacity, screw terminals, IP20 front, 45 mm wide.","salesMarkdown":"The overload release is thermal (bimetal), the short-circuit trip is magnetic — the standard combo for motor branch-circuit protection. No ground-fault detection on this variant. Wire range accepts 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²) — covers most motor feeder sizes up to 2.5 mm². AWG equivalent is 2x (18 to 14). Mounting position is any orientation. Zero clearance needed at the sides or back for heat dissipation, which simplifies panel layout. This breaker's interrupting rating varies sharply with voltage: 100 kA at 240 V AC, 50 kA at 400 V AC, dropping to 3 kA at 500 V and 2 kA at 690 V. At 690 V the 2 kA rating is low; if your panel sees high fault current at that voltage, this isn't the right breaker. Rated impulse withstand voltage is 6 kV, which covers typical surge environments in industrial control panels. RoHS compliance date is 01/01/2013, meaning it meets the EU substance restrictions that took effect that year. No UL or CSA listing is stated in the evidence, but the part carries the Siemens SIRIUS brand and is designed to IEC/EN 60947 standards common in European-sourced panels. ## Panel integration Width is 45 mm — three 15 mm modules on a DIN rail, standard for a 3-pole motor-protective device. Depth is 81 mm, height 90 mm. Power dissipation at rated current is 9.25 W total, 3.1 W per pole in hot operating state. That's moderate for a 10 A breaker — account for it in enclosure thermal calculations, especially if multiple units are ganged without spacing. An auxiliary switch can be added (product extension auxiliary switch is supported).","metaTitle":"Siemens 3RV1011-1JK10-0AA1 SIRIUS Circuit Breaker, 10 A, 4 k","metaDescription":"Siemens SIRIUS 3RV1011-1JK10-0AA1 circuit breaker. 10 A continuous, 4 kW motor rating at 400 V AC. 50 kA breaking capacity at 400 V. Screw terminals, IP20 front. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Backwards":"0 mm","At The Side":"0 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"4 kW","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"9.25 W","Substance Prohibitance (Date)":"01/01/2013","Continuous Current Rated Value":"10 A","Design Of The Overload Release":"thermal","at AWG cables for main contacts":"2x (18 ... 14)","Design Of The Short-Circuit Trip":"magnetic","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AC in hot operating state per pole":"3.1 W","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"10 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"thermomagnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"90 A","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"100 000","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0c8d4870c39527a91cbee9dc73cfaa40.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=312282&mlfb=3RV1011-1JK10-0AA1","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JK10-0AA1/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RV1011-1JK10-0AA1?","answer":"The 3RV1011-1HA10 is a peer in the same SIRIUS family. The key difference is the current rating — the 1JK10 is 10 A, the 1HA10 is a different amp rating. Check the specific continuous current and motor power rating before substituting; the footprint and terminal layout are the same."},{"question":"Will 3RV1011-1JK10-0AA1 drop into a panel specified for 3RV1011-1HA10?","answer":"Yes, the mechanical dimensions are identical — 45 mm wide, 90 mm high, 81 mm deep, same DIN-rail mounting. The wiring terminals accept the same wire sizes. The substitution depends on whether the amp rating matches your motor load."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1JK10-0AA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1JK10-0AA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}