{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1JK15-0AA1","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1JK15-0AA1","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1JK15-0AA1","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JK15-0AA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV1011-1JK15-0AA1, 10 A continuous, 100 kA breaking at 240 V AC, screw terminals, thermal-magnetic, phase failure detection.","salesMarkdown":"The Siemens SIRIUS 3RV1011-1JK15-0AA1 is a motor-protective circuit breaker rated for 10 A continuous current. It combines a thermal overload release (for sustained overcurrent) with a magnetic short-circuit trip (for fault clearing), and includes phase failure detection. Screw-type terminals on both the main and auxiliary circuits accept solid conductors 2x (0.5 … 1.5 mm²) or 2x (0.75 … 2.5 mm²), and stranded the same. Zero clearance needed at the back or sides — the breaker can be packed tight against adjacent devices. ## Auxiliary switch and control ratings The auxiliary switch is transverse design and can be extended with an additional switch module. Contact ratings: 1 A at 24 V, 0.5 A at 230 V, and 0.15 A at 60 V — these are the switching currents for the control circuit, not the main power path. The rated voltage range for the main circuit is 20 … 690 V AC, and the maximum operating frequency in AC-3 duty is 15 operations per hour. Shock resistance is 25 g for 11 ms. Front-side protection is IP20 — suitable for enclosed panels, not for washdown. The part is RoHS compliant with a substance prohibition date of 01/01/2013. No ground fault detection is built in.","metaTitle":"Siemens SIRIUS 3RV1011-1JK15-0AA1 Circuit Breaker, 10 A, 100","metaDescription":"Siemens SIRIUS 3RV1011-1JK15-0AA1 circuit breaker, 10 A continuous, 100 kA breaking at 240 V. Thermal-magnetic, phase failure detection. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","at 24 V":"1 A","at 60 V":"0.15 A","Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","at 230 V":"0.5 A","Backwards":"0 mm","At The Side":"0 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"4 kW","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"9.25 W","Substance Prohibitance (Date)":"01/01/2013","Continuous Current Rated Value":"10 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Design Of The Short-Circuit Trip":"magnetic","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AC in hot operating state per pole":"3.1 W","for AWG cables for auxiliary contacts":"2x (18 ... 14)","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","operational current at AC-3 at 400 V rated value":"10 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"thermomagnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"90 A","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Operating Cycles) Of The Main Contacts Typical":"100 000","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3f06d82b8abda3d51d06e83bb22ba303.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=65575&mlfb=3RV1011-1JK15-0AA1","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1JK15-0AA1/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV1011-1JK15-0AA1 at 400 V?","answer":"At 400 V AC the breaking capacity is 50 kA. At 240 V it is 100 kA, at 500 V it is 3 kA, and at 690 V it is 2 kA."},{"question":"Will 3RV1011-1JK15-0AA1 drop into a panel specified around 3RV1011-1HA10?","answer":"Both are 45 mm wide SIRIUS breakers on the same DIN-rail footprint, so the mechanical fit is the same. The 1JK15-0AA1 carries a 10 A continuous rating and 100 kA breaking at 240 V; the 1HA10 is a different variant — verify the load current and fault-current coordination before swapping."},{"question":"How do I get current pricing and availability for 3RV1011-1JK15-0AA1?","answer":"Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time through independent distribution channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1JK15-0AA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1JK15-0AA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}