{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-1KA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-1KA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-1KA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1KA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV1011-1KA10-ZX95, CLASS 10, screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715.","salesMarkdown":"## Where it fits — panel and pit Clearance requirements: 20 mm upward and downward, 9 mm to the side, zero forward and backward. The screw-type terminals for the main current circuit accept 2x (0.5... 1.5 mm²) solid or stranded, or 2x (0.75... 2.5 mm²) — M3 screws for the main contacts. ## Breaking capacity — what it can interrupt Short-circuit breaking capacity varies with line voltage, and this breaker is rated for the full range: 100 kA at 240 V, 13 kA at 400 V, 3 kA at 500 V, and 2 kA at 690 V. The backup fuse ratings for gL/gG fuses are 80 A at 240 V and 400 V, stepping down to 50 A at 500 V and 690 V.","metaTitle":"Siemens 3RV1011-1KA10-ZX95 Motor Protection Circuit Breaker,","metaDescription":"Siemens SIRIUS 3RV1011-1KA10-ZX95 motor protection circuit breaker. CLASS 10 trip, 100 kA at 240 V. Screw/snap-on 35 mm DIN rail. Phase failure detection. Sourced to order. Request","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"gL/gG 80 A","at 400 V":"gL/gG 80 A","at 500 V":"gL/gG 50 A","at 690 V":"gL/gG 50 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"2 hp","at 240 V rated value":"100 kA","at 400 V rated value":"13 kA","at 480 V rated value":"12 A","at 500 V rated value":"3 kA","at 600 V rated value":"12 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"8 hp","at 575/600 V rated value":"10 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"12 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"12 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"12.5 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Switching Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"156 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"9 ... 12.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4d9c74415e42a04557e9c1e5176826af.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=5251&mlfb=3RV1011-1KA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-1KA10-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3RV1011-1KA10-ZX95 and how is it quoted?","answer":"We source this part through independent distribution channels. Submit an RFQ for current pricing and availability — quoted to order against your specific quantity and delivery needs."},{"question":"What is the closest functional alternative to 3RV1011-1KA10-ZX95?","answer":"The 3RV1011-1HA10 is a close sibling in the same SIRIUS family. The key difference is the -ZX95 suffix indicates a special version — verify the specific rating and accessory compatibility before substituting. The 3RV1011-0HA10 and 3RV1011-0GA10 are also related, but check the trip class and current range against your motor nameplate."},{"question":"Will 3RV1011-1KA10-ZX95 drop into a panel specified around 3RV1011-1HA10?","answer":"Both share the same SIRIUS 3RV10 platform with identical 45 mm width and screw/snap-on DIN rail mounting. The -ZX95 variant may have a different current setting range or special factory settings. Physically it fits the same footprint and rail slot, but verify the thermal rating matches your motor FLA before committing the BOM line."},{"question":"What compliance documentation does this brand provide?","answer":"As a Siemens SIRIUS component, standard compliance documentation includes CE marking for the Low Voltage Directive and RoHS compliance. Specific UL, CSA, or IEC certificates should be available from the manufacturer's support portal using the order code. We can include available compliance declarations with your shipment upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-1KA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-1KA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}