{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-4AA10-0AA4","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-4AA10-0AA4","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-4AA10-0AA4","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-4AA10-0AA4","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-4AA10-0AA4, motor protection circuit breaker, CLASS 10, 13 kA at 400 V AC, screw and snap-on mounting onto 35 mm DIN rail, 45 mm width, 75 mm depth.","salesMarkdown":"The lower 13 kA figure is the unconditional breaking capacity; the 50 kA figure applies when coordinated with an upstream fuse or breaker (type 2 coordination). For a 480 V system, the interrupting rating drops to 16 A, meaning this is sized for the motor's full-load current, not the fault level. No ground fault detection, so if that's required, add a separate ground-fault relay or choose a variant with that feature. Screw-type terminals for the main current circuit accept 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded wire. Use a PZ1 or PZ2 screwdriver with a 5 to 6 mm shaft diameter. The M3 terminal screws are standard for this class; torque them to the manufacturer's specification (not listed here, but typically 0.8 to 1.2 Nm for M3 in this series).","metaTitle":"Siemens 3RV1011-4AA10-0AA4 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-4AA10-0AA4 motor protection circuit breaker. CLASS 10 trip, 13 kA breaking capacity at 400 V AC, phase failure detection. Active production, available to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"gG 80 A","at 400 V":"gG 80 A","at 500 V":"gG 50 A","at 690 V":"gG 50 A","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"3 kW","at 240 V rated value":"100 kA","at 400 V rated value":"13 kA","at 480 V rated value":"16 A","at 500 V rated value":"3 kA","at 600 V rated value":"16 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"3 kA","at AC at 690 V rated value":"2 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"16 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"16 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"16 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"156 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"10 ... 16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9d6f41561e63d3a4ecbe4d943e6f0df7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=231123&mlfb=3RV1011-4AA10-0AA4","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-4AA10-0AA4/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV1011-4AA10-0AA4 drop into a panel specified for 3RV1011-1HA10?","answer":"The 3RV1011-4AA10-0AA4 shares the same 45 mm width, 75 mm depth, and 35 mm DIN-rail mounting as the 3RV1011-1HA10, so the physical footprint is identical. However, the 4AA10 variant includes phase failure detection and has different thermal/ magnetic trip settings — verify the motor FLA and short-circuit rating against the existing coordination study before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-4AA10-0AA4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-4AA10-0AA4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}