{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1021-0BA15-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1021-0BA15-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RV1021-0BA15-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1021-0BA15-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1021-0BA15-ZW98, 0.2 A continuous rated current, CLASS 10 trip, 100 kA breaking capacity at 400 V AC, screw terminals, IP20 front.","salesMarkdown":"It is rated for a continuous current of 0.2 A and trips in CLASS 10, meaning it will clear a stalled-rotor overload within 10 seconds at 7.2× rated current — fast enough to protect small motors without nuisance tripping on normal starts. Breaking capacity sits at 100 kA across the board — at 240 V, 400 V, 500 V, and 690 V AC — so it handles high-fault-current panels without cascading upstream. The 690 V rated insulation voltage matches the maximum circuit voltage in many industrial motor branches. Depth is 96 mm, so check enclosure depth if you're retrofitting into a shallow gland box. Solid wire accepts 2× (0.5…1.5 mm²) and 2× (0.75…2.5 mm²); stranded accepts 2× (1…2.5 mm²) and 2× (2.5…6 mm²). AWG for main contacts is 2× (14…10). The auxiliary switch is transverse design and the product extension supports adding auxiliary switches. IP20 on the front — sealed against fingers but not dust or washdown. Shock rated at 25g / 11 ms. Substance prohibitance date is 01.05.2012 — RoHS compliance is implied for that EU effective date.","metaTitle":"Siemens 3RV1021-0BA15-ZW98 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1021-0BA15-ZW98 motor protection circuit breaker, 0.2 A continuous, CLASS 10 trip, 100 kA breaking at 400 V. Active production. Sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"97 mm","at 24 V":"1 A","at 60 V":"0.15 A","Stranded":"2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)","at 230 V":"0.5 A","Backwards":"0 mm","Trip Class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"0.06 kW","Design Of The Product":"for motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"5.5 W","Substance Prohibitance (Date)":"01.05.2012","Continuous Current Rated Value":"0.2 A","Design Of The Auxiliary Switch":"transverse","at AWG cables for main contacts":"2x (14 ... 10)","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AWG cables for auxiliary contacts":"2x (18 ... 14)","at AC in hot operating state per pole":"1.8 W","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"0.2 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"thermomagnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"100 000","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.14 ... 0.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=303155&mlfb=3RV1021-0BA15-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1021-0BA15-ZW98/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1021-0BA15-ZW98 and how do I get a price?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the breaking capacity of this breaker?","answer":"100 kA at 240 V, 400 V, 500 V, and 690 V AC — the same rating across all listed voltages."},{"question":"What compliance documentation does this brand provide for 3RV1021-0BA15-ZW98?","answer":"The substance prohibitance date of 01.05.2012 indicates RoHS compliance per EU Directive 2011/65/EU. Phase failure detection is included; ground fault detection is not."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1021-0BA15-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1021-0BA15-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}