{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1021-0GA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1021-0GA15","canonicalUrl":"https://aoctrl.com/siemens/3RV1021-0GA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1021-0GA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1021-0GA15, 0.63 A rated continuous current, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw-type terminals, DIN rail mount.","salesMarkdown":"The Siemens 3RV1021-0GA15 is a SIRIUS motor protection circuit breaker rated for 0.63 A continuous current with a Class 10 trip characteristic. It delivers 100 kA breaking capacity across the 240 V to 690 V AC range, so it handles high-fault-current installations without cascading to upstream devices. Phase failure detection is built in — the breaker trips on a lost phase before the motor single-phases to failure. ## Mounting and integration Snap-on mounting onto 35 mm DIN rail per EN 50022, with screw-type terminals for the main circuit and auxiliary/control circuit. The 45 mm width and 96 mm depth fit standard panel spacing; mounting position is any, so it works in vertical or horizontal busway layouts. Screw terminals accept solid conductors 2x (0.5–1.5 mm²) and 2x (0.75–2.5 mm²), or stranded 2x (1–2.5 mm²) and 2x (2.5–6 mm²).","metaTitle":"Siemens 3RV1021-0GA15 SIRIUS Motor Protection CB, 0.63 A, Cl","metaDescription":"Siemens 3RV1021-0GA15 SIRIUS motor protection circuit breaker, 0.63 A rated current, Class 10 trip, 100 kA breaking capacity at 400 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"97 mm","at 24 V":"1 A","at 60 V":"0.15 A","Stranded":"2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)","at 230 V":"0.5 A","Backwards":"0 mm","Trip Class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"0.18 kW","Design Of The Product":"for motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"5.5 W","Substance Prohibitance (Date)":"01.05.2012 00:00:00","Continuous Current Rated Value":"0.63 A","Design Of The Auxiliary Switch":"transverse","at AWG cables for main contacts":"2x (14 ... 10)","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AWG cables for auxiliary contacts":"2x (18 ... 14)","at AC in hot operating state per pole":"1.8 W","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"0.63 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"thermomagnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Product Function Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"100 000","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.45 ... 0.63 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=18731&mlfb=3RV1021-0GA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1021-0GA15/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV1021-0GA15?","answer":"100 kA at 240 V, 400 V, 500 V, and 690 V AC — consistent across the full voltage range, so no derating needed at higher voltages."},{"question":"Does 3RV1021-0GA15 detect phase failure?","answer":"Yes, phase failure detection is included. The breaker will trip if one phase is lost, protecting the motor from single-phasing."},{"question":"Where can I buy 3RV1021-0GA15 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1021-0GA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1021-0GA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}