{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1021-1JA15-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1021-1JA15-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1021-1JA15-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1021-1JA15-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1021-1JA15-ZX95, motor protection circuit breaker, 10 A continuous rated current, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw-type terminals, 45 x 97 x 96 mm.","salesMarkdown":"Zero clearance required at the sides and rear, so it packs tight on a DIN rail without forced air gaps. Any mounting position allowed, which simplifies layout in crowded enclosures. ## Termination and wiring Solid wire range: 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²); stranded: 2x (1 to 2.5 mm²) and 2x (2.5 to 6 mm²). AWG equivalent for main contacts is 2x (14 to 10). The dual-wire capacity per clamp is useful when looping through to a downstream contactor or control relay — no separate terminal block needed for the pass-through.","metaTitle":"Siemens 3RV1021-1JA15-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1021-1JA15-ZX95 SIRIUS motor protection circuit breaker, 10 A continuous, Class 10 trip, 100 kA breaking at 400 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"97 mm","at 24 V":"1 A","at 60 V":"0.15 A","Stranded":"2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)","at 230 V":"0.5 A","Backwards":"0 mm","Trip Class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"4 kW","Design Of The Product":"for motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"42 kA","at AC at 690 V rated value":"6 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"9.25 W","Substance Prohibitance (Date)":"01.05.2012","Continuous Current Rated Value":"10 A","Design Of The Auxiliary Switch":"transverse","at AWG cables for main contacts":"2x (14 ... 10)","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AWG cables for auxiliary contacts":"2x (18 ... 14)","at AC in hot operating state per pole":"3.1 W","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"10 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"thermomagnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"100 000","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=325198&mlfb=3RV1021-1JA15-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1021-1JA15-ZX95/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RV1021-1JA15-ZX95?","answer":"Submit an RFQ against this order code; the part is sourced through independent distribution and availability with current pricing is confirmed at quote time."},{"question":"What is 3RV1021-1JA15-ZX95's listed depth?","answer":"Depth is 96 mm, width 45 mm, height 97 mm."},{"question":"What solid wire sizes does 3RV1021-1JA15-ZX95 accept?","answer":"Solid wire: 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²). Stranded: 2x (1 to 2.5 mm²) and 2x (2.5 to 6 mm²)."},{"question":"Will 3RV1021-1JA15-ZX95 drop into a panel specified around 3RV2021-1FA15 without rewiring?","answer":"Both are SIRIUS motor protection breakers with the same 45 mm width and snap-on DIN rail mounting, but the 3RV2021-1FA15 is a higher-current variant (typically 22 A continuous). The 3RV1021-1JA15-ZX95 is rated 10 A continuous, so it fits the same footprint but only if the motor FLA is within its range. Terminal wire ranges are similar; no rewiring of the DIN rail or enclosure cutout is needed."},{"question":"What compliance documentation does Siemens provide for 3RV1021-1JA15-ZX95?","answer":"The part carries a substance prohibition date of 01.05.2012, indicating RoHS compliance per EU Directive 2011/65/EU. Full documentation (UL, CSA, CE, IEC) is available from Siemens via the product datasheet and certificate portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1021-1JA15-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1021-1JA15-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}