{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1341-4HC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1341-4HC10","canonicalUrl":"https://aoctrl.com/siemens/3RV1341-4HC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1341-4HC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1341-4HC10 circuit breaker for starter combinations, 3-pole, 50 A continuous, 22 kW at 400 V, 50 kA breaking capacity at 400 V, screw terminals, DIN rail mount, IP20 front.","salesMarkdown":"The 50 kA breaking capacity at 400 V is the figure that governs SCCR for the branch circuit; at 240 V it rises to 100 kA, and at 690 V it drops to 6 kA — so verify the available fault current at your installation voltage. The 70 mm width and 165 mm height fit a standard MCC bucket or small enclosure; depth is 174 mm, so allow clearance for the box terminals and wiring. Any mounting position is permitted — no derating for horizontal or vertical orientation. Main circuit terminals accept solid conductors 2x (2.5 … 16 mm²) and stranded 2x (10 … 50 mm²) or 1x (10 … 70 mm²). AWG equivalents: 2x (10 … 1) solid, 1x (10 … 2) stranded. Auxiliary and control circuit terminals are screw-type as well. The box-terminal design on the main circuit provides a secure connection for larger cable sizes typical of a 50 A motor branch. Shock resistance 25g / 11 ms. RoHS compliance date (substance prohibition) 07/01/2006. Surge voltage resistance rated 6 000 V. The part carries finger-safe touch protection against electrical shock.","metaTitle":"Siemens 3RV1341-4HC10 SIRIUS Circuit Breaker, 50 A, 50 kA @","metaDescription":"Siemens 3RV1341-4HC10 SIRIUS circuit breaker for starter combinations. 50 A continuous, 22 kW at 400 V, 50 kA breaking capacity. DIN rail mount, IP20 front. Current lifecycle. Avai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"174 mm","Solid":"2x (2.5 ... 16 mm²)","Width":"70 mm","Height":"165 mm","Stranded":"2x (10 ... 50 mm²), 1x (10 ... 70 mm²)","Backwards":"0 mm","At The Side":"0 mm","Rated Value":"690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"22 kW","Design Of The Product":"for starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals with box terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"50 kA","at AC at 500 V rated value":"12 kA","at AC at 690 V rated value":"6 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"27 W","Substance Prohibitance (Date)":"07/01/2006","Continuous Current Rated Value":"50 A","at AWG cables for main contacts":"2x (10 ... 1), 1x (10 ... 2)","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AC in hot operating state per pole":"9 W","Finely Stranded With Core End Processing":"2x (2.5 ... 35 mm²), 2.5 ... 50 mm²","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"50 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"magnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"50 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=274388&mlfb=3RV1341-4HC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1341-4HC10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1341-4HC10?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3RV1341-4HC10 at 400 V?","answer":"50 kA at 400 V AC. At 240 V it is 100 kA, at 500 V it is 12 kA, and at 690 V it is 6 kA."},{"question":"Does 3RV1341-4HC10 include ground fault or phase failure detection?","answer":"No — ground fault detection and phase failure detection are both listed as 'No'."},{"question":"What compliance documentation is available for 3RV1341-4HC10?","answer":"RoHS compliance date is 07/01/2006. The part is designed to IEC/EN standards for circuit breakers and carries IP20 finger-safe touch protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1341-4HC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1341-4HC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}