{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1353-6JP10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1353-6JP10","canonicalUrl":"https://aoctrl.com/siemens/3RV1353-6JP10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1353-6JP10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1 molded case circuit breaker, 3RV1353-6JP10, for starter combinations, 12.5 A rated current, 85 kA interrupting capacity at 400 V AC, 3-pole, screw terminals, IP20 front protection.","salesMarkdown":"Per the datasheet, it is a 3-pole unit rated 12.5 A continuous current, with a magnetic overcurrent release set non-adjustable at 13 × In for short-circuit protection. Auxiliary contacts are screw-type as well, though the unit ships without auxiliary contact blocks fitted — the provision is there for field addition. The front face carries an IP20 rating, meaning finger-safe access to the operator handle and trip indicator, but the body itself is not sealed against moisture ingress; this is a panel-interior component, not a washdown-duty device. For a 400 V distribution system with a transformer upstream capable of delivering 85 kA of prospective fault current, this breaker holds coordination. The ratings step down at higher voltages: 100 kA at 240 V, 50 kA at 500 V, and 10 kA at 690 V AC. The magnetic release is fixed at 13 × In, which for a 12.5 A breaker means a magnetic trip threshold of approximately 162.5 A. That is a narrow instantaneous band, typical for motor-starting applications where you want the breaker to ride through inrush but trip fast on a bolted fault. The mechanical endurance is rated at 25,000 operations for the main contacts — a figure that assumes the breaker is switched under load within its AC-3 duty cycle (15 operations per hour maximum at AC-3). Below that switching rate, contact life extends proportionally. Surge voltage withstand is 8,000 V. Shock resistance is 12 g for 11 ms. The breaker measures 90 mm wide × 130 mm high × 70 mm deep. It mounts via screw fixing. Clearance required is zero mm backwards and zero mm at the side.","metaTitle":"Siemens 3RV1353-6JP10 MCCB, 12.5 A, 85 kA at 400 V","metaDescription":"Siemens SIRIUS 3RV1353-6JP10 molded case circuit breaker for starter combinations. Rated 12.5 A, 85 kA SCCR at 400 V AC. Screw terminals, IP20 front. Current production. Available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"70 mm","Width":"90 mm","Height":"130 mm","Maximum":"2 000 m","Backwards":"0 mm","At The Side":"0 mm","Rated Value":"690 V","On The Front":"IP20","Mounting type":"screw fixing","During Storage":"-40 ... +70 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","Auxiliary switch":"Yes","During Operation":"-25 ... +70 °C","During Transport":"-40 ... +70 °C","Shock resistance":"12g / 11 ms","Mounting position":"any","Product brand name":"SIRIUS","Product designation":"molded-case circuit breaker","at 400 V rated value":"5.5 kW","Design of the product":"for starter combinations","For Auxiliary Contacts":"0","Ground fault detection":"No","Phase failure detection":"No","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"85 kA","at AC at 500 V rated value":"50 kA","at AC at 690 V rated value":"10 kA","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"25 000","Continuous current rated value":"12.5 A","Surge voltage resistance rated value":"8 000 V","Number of poles for main current circuit":"3","For Auxiliary And Control Current Circuit":"screw-type terminals","Removable Terminal For Auxiliary And Control Circuit":"No","Design of the overcurrent release and short-circuit release":"magnetic","Arrangement of electrical connectors for main current circuit":"front side"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=209952&mlfb=3RV1353-6JP10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1353-6JP10/alternatives.json"},"ai":{"faq":[{"question":"What are the mounting dimensions for 3RV1353-6JP10?","answer":"The breaker measures 90 mm wide × 130 mm high × 70 mm deep. It uses screw fixing — not DIN-rail snap-on — so the mounting plate must be drilled for the screw pattern. Zero mm clearance is required backwards or at the sides."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1353-6JP10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1353-6JP10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}