{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1353-6MM10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1353-6MM10","canonicalUrl":"https://aoctrl.com/siemens/3RV1353-6MM10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1353-6MM10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS molded-case circuit breaker, 3RV1353-6MM10, 32 A continuous, 690 V rated, 85 kA breaking capacity at 400 V AC, for starter combinations.","salesMarkdown":"Rated for 32 A continuous current and 690 V maximum, it handles motor loads up to 15 kW at 400 V AC-3 duty, so it's sized for common 30 A motor branch circuits in industrial control panels. The breaking capacity tells you where it can safely interrupt a fault: 100 kA at 240 V, 85 kA at 400 V, 50 kA at 500 V, and 10 kA at 690 V AC — that 85 kA at 400 V is the figure most panel builders will check against the available fault current at the distribution board. Main circuit terminals are screw-type on the front side; auxiliary and control circuit terminals are also screw-type. The design accepts an auxiliary switch add-on (not included), and the overcurrent release is magnetic-only — no thermal bimetal, so it's a magnetic-only instantaneous trip for short-circuit protection, relying on the upstream contactor or overload relay for thermal overload. ## Environmental limits and compliance Operates from -25 to +70 °C, stores and ships from -40 to +70 °C, with a maximum installation altitude of 2000 m above sea level. Shock resistance is 12 g for 11 ms — adequate for most fixed-mount industrial panels but not rated for continuous vibration on moving equipment. The substance prohibition date of 08.01.2008 indicates RoHS compliance per the EU directive effective from that date.","metaTitle":"Siemens 3RV1353-6MM10 SIRIUS MCCB, 32 A, 690 V, 85 kA","metaDescription":"Siemens 3RV1353-6MM10 SIRIUS molded-case circuit breaker, 32 A continuous, 85 kA breaking capacity at 400 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"70 mm","Width":"90 mm","Height":"130 mm","Backwards":"0 mm","At The Side":"0 mm","Rated Value":"690 V","During Storage":"-40 ... +70 °C","lifecycle_stage":"current","During Operation":"-25 ... +70 °C","During Transport":"-40 ... +70 °C","Fastening Method":"screw fixing","Shock Resistance":"12g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"molded-case circuit breaker","at 400 V rated value":"15 kW","Design Of The Product":"for starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"85 kA","at AC at 500 V rated value":"50 kA","at AC at 690 V rated value":"10 kA","at AC-3 rated value maximum":"690 V","Substance Prohibitance (Date)":"08.01.2008","Continuous Current Rated Value":"32 A","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"8 000 V","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"32 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"magnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"25 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=46828&mlfb=3RV1353-6MM10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1353-6MM10/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV1353-6MM10 at 400 V?","answer":"85 kA at 400 V AC, which is the rating most panel builders will check against the available fault current at the distribution board. It also carries 100 kA at 240 V, 50 kA at 500 V, and 10 kA at 690 V."},{"question":"Can 3RV1353-6MM10 be mounted directly against other components?","answer":"Yes — the required clearance at the back and sides is 0 mm, so it can sit flush against the backplate or adjacent devices without derating for airflow blockage."},{"question":"Where can I buy 3RV1353-6MM10 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price."},{"question":"Does 3RV1353-6MM10 include an auxiliary switch?","answer":"The design accepts an auxiliary switch as a product extension (Yes), but it is not included with the base order code. The auxiliary and control circuit terminals are screw-type and ready for the add-on."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1353-6MM10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1353-6MM10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}