{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1353-6PM10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1353-6PM10","canonicalUrl":"https://aoctrl.com/siemens/3RV1353-6PM10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1353-6PM10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RV1353-6PM10, molded case circuit breaker for starter combination, 52 A rated current, Icu = 85 kA at 400 V, 3-pole, screw terminal with phase barriers.","salesMarkdown":"Rated at 52 A continuous current (In) and an ultimate breaking capacity Icu of 85 kA at 400 V, this 3-pole unit clears high-fault currents without cascading damage upstream. The magnetic release is adjustable between 6 and 13 times In, so you tune the instantaneous trip threshold to match the motor inrush without nuisance tripping on a healthy start. Screw terminals and included phase barriers simplify panel wiring and maintain phase-to-phase clearance. ## Deployment context The screw terminals accept lug or box-type conductors, and the phase barriers are factory-fitted — no extra assembly to maintain the 85 kA withstand rating. No auxiliary switch, no ground-fault detection, no phase-failure detection, and no removable control-circuit terminal are built in; if those functions are needed, they must be added externally or the panel design must account for separate monitoring.","metaTitle":"Siemens 3RV1353-6PM10 MCCB, 52A, 85kA at 400V, Screw Termina","metaDescription":"Siemens 3RV1353-6PM10 molded case circuit breaker, 52A rated current, Icu=85kA at 400V, adjustable magnetic release 6-13xIn, 3-pole, screw terminals with phase barriers. Lifecycle","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"lifecycle_stage":"current","Auxiliary switch":"No","Ground fault detection":"No","Phase failure detection":"No","Removable Terminal For Auxiliary And Control Circuit":"No"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=332231&mlfb=3RV1353-6PM10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1353-6PM10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1353-6PM10 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional alternative to 3RV1353-6PM10?","answer":"The Siemens 3VA1010-2ED36-0AC0 is a SENTRON MCCB with a 100 A frame, 2 auxiliary switches, and a TM210 thermal-magnetic release. It offers higher continuous current (100 A) and similar breaking capacities (52.5 kA at 240 V, 32 kA at 415 V) but is a line-protection device, not a starter-combination breaker. Panel rewiring would be required due to different terminal arrangements and footprint."},{"question":"Does 3RV1353-6PM10 include an auxiliary switch?","answer":"No, this breaker does not include an auxiliary switch."},{"question":"What is the breaking capacity Icu of 3RV1353-6PM10?","answer":"The ultimate breaking capacity Icu is 85 kA at 400 V AC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1353-6PM10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1353-6PM10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}