{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1364-7AN10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1364-7AN10","canonicalUrl":"https://aoctrl.com/siemens/3RV1364-7AN10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1364-7AN10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS molded-case circuit breaker, 3RV1364-7AN10, 100 A continuous current, 200 kA breaking capacity at 400 V AC, for starter combinations, screw fixing.","salesMarkdown":"## SIRIUS 3RV1364-7AN10 — 100 A MCCB for Starter Combinations The short-circuit trip is electronic, which gives more precise coordination with downstream contactors and overload relays compared to thermal-magnetic designs. The breaking capacity varies by line voltage: 100 kA at 240 V AC, 200 kA at 400 V AC, 150 kA at 500 V AC, and 80 kA at 690 V AC. At 690 V, the 80 kA rating still covers most heavy industrial applications. The AC-3 operational current at 400 V is 100 A, matching the continuous rating — so the motor load and the breaker rating align without derating for typical induction motor starting duty. ## Environmental and Installation Constraints Shock resistance is 12 g for 11 ms, which is standard for industrial panel mounting. Maximum installation altitude is 2,000 m above sea level — above that, dielectric strength and current-carrying capacity derate per IEC 60947. The main and auxiliary/control circuits both use screw-type terminals, so expect to torque per the manufacturer's spec on the nameplate. The breaker accepts auxiliary switch modules, but this base unit ships with zero built-in contacts — you add what the circuit needs.","metaTitle":"Siemens 3RV1364-7AN10 SIRIUS MCCB, 100 A, 200 kA at 400 V","metaDescription":"Siemens 3RV1364-7AN10 SIRIUS molded-case circuit breaker, 100 A continuous, 200 kA breaking at 400 V AC. Active lifecycle, screw fixing, finger-safe. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"103.5 mm","Width":"105 mm","Height":"205 mm","Backwards":"0 mm","At The Side":"0 mm","Rated Value":"20 ... 690 V","During Storage":"-40 ... +70 °C","lifecycle_stage":"current","During Operation":"-25 ... +70 °C","During Transport":"-40 ... +70 °C","Fastening Method":"screw fixing","Shock Resistance":"12g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"molded-case circuit breaker","at 400 V rated value":"55 kW","Design Of The Product":"for starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"200 kA","at AC at 500 V rated value":"150 kA","at AC at 690 V rated value":"80 kA","at AC-3 rated value maximum":"690 V","Substance Prohibitance (Date)":"01/08/2008","Continuous Current Rated Value":"100 A","Design Of The Short-Circuit Trip":"electronic","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"8 000 V","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"100 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"electronic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"1 000 A","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Operating Cycles) Of The Main Contacts Typical":"20 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=165955&mlfb=3RV1364-7AN10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1364-7AN10/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV1364-7AN10 at 400 V?","answer":"200 kA at 400 V AC, which is the highest rating in its voltage range and suits high-fault-capacity installations."},{"question":"Where can I buy 3RV1364-7AN10?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1364-7AN10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1364-7AN10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}