{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1383-7JN10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1383-7JN10","canonicalUrl":"https://aoctrl.com/siemens/3RV1383-7JN10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1383-7JN10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS molded-case circuit breaker, 3RV1383-7JN10, 630 A continuous, 100 kA breaking at 400 V AC, for starter combinations.","salesMarkdown":"It delivers 100 kA breaking capacity at 400 V AC and 240 V AC, 65 kA at 500 V AC, and 30 kA at 690 V AC — numbers that tell you it handles high-fault industrial feeders without cascading upstream. The electronic short-circuit trip gives precise, repeatable response across the fault curve. ## Panel integration & mounting Mounts via screw fixing in any position — no DIN-rail clip here, so plan for direct panel or backplate drilling. The footprint is 210 mm wide by 268 mm tall by 103.5 mm deep, with zero clearance required at the back or sides for airflow or arc chutes. That 103.5 mm depth matters when you're fitting it into a shallow enclosure or a gland-plate layout. ## Duty & ratings The AC-3 operational current at 400 V matches the continuous rating at 630 A, so motor-switching duty doesn't force a derate. Maximum switching frequency is 15 operations per hour — fine for pump, fan, and compressor starts, not for rapid cycling. Rated operational voltage spans 20 to 690 V AC, with surge voltage resistance at 8 kV. Shock resistance is 12 g for 11 ms, and installation altitude is limited to 2,000 m above sea level.","metaTitle":"Siemens 3RV1383-7JN10 SIRIUS MCCB, 630 A, 100 kA at 400 V","metaDescription":"Siemens 3RV1383-7JN10 SIRIUS molded-case circuit breaker, 630 A continuous, 100 kA breaking at 400 V AC. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"103.5 mm","Width":"210 mm","Height":"268 mm","Backwards":"0 mm","At The Side":"0 mm","Rated Value":"20 ... 690 V","During Storage":"-40 ... +70 °C","lifecycle_stage":"current","During Operation":"-25 ... +50 °C","During Transport":"-40 ... +70 °C","Fastening Method":"screw fixing","Shock Resistance":"12g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"molded-case circuit breaker","at 400 V rated value":"355 kW","Design Of The Product":"for starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"65 kA","at AC at 690 V rated value":"30 kA","at AC-3 rated value maximum":"690 V","Substance Prohibitance (Date)":"01/08/2008","Continuous Current Rated Value":"630 A","Design Of The Short-Circuit Trip":"electronic","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"8 000 V","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"630 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"electronic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"6 300 A","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"20 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=196150&mlfb=3RV1383-7JN10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1383-7JN10/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV1383-7JN10 at 400 V?","answer":"100 kA at 400 V AC, matching the rating at 240 V AC. At 500 V it drops to 65 kA, and at 690 V to 30 kA."},{"question":"Where can I buy 3RV1383-7JN10 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number."},{"question":"What compliance documentation does Siemens provide for 3RV1383-7JN10?","answer":"The part carries a substance prohibitance date of 01/08/2008, indicating RoHS compliance. Standard Siemens documentation includes the declaration of conformity, CE marking, and UL/CSA file listings per the SIRIUS product family."},{"question":"Will 3RV1383-7JN10 drop into a panel specified for 3RV1011-0GA10?","answer":"No — the 3RV1383-7JN10 is a much larger frame (210 x 268 x 103.5 mm versus the 3RV1011 series compact size) and uses screw fixing rather than DIN-rail mounting. Rewiring and panel layout changes are required."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1383-7JN10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1383-7JN10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}