{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0AA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0AA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0AA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0AA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-0AA10-ZX95, Class 10 trip, S00 frame, 45 mm width, 97 mm depth, screw and snap-on DIN rail mounting.","salesMarkdown":"## Motor protection circuit breaker, SIRIUS series, S00 frame The Siemens 3RV2011-0AA10-ZX95 is a SIRIUS motor protection circuit breaker in the S00 frame size, designed for motor protection with Class 10 trip characteristics. The unit occupies 45 mm width and 97 mm depth on the rail, with 50 mm clearance required above and below for ventilation and arc-quenching. ## Trip class and protection features Class 10 trip means the bimetal releases within 10 seconds at 7.2× rated current — the standard for standard-duty induction motors starting against light loads. Ground fault detection is not included; for ground-fault protection, pair this breaker with a separate ground-fault relay or use a 3RV2 variant with the GF module. ## Voltage and breaking capacity Rated insulation voltage spans 20 to 690 V. The breaking capacity at 400 V AC is 100 kA, which covers most industrial distribution panels with transformer ratings up to 2 MVA. At 240 V AC the interrupting rating is also 100 kA. The 100 kA figure holds at 500 V and 690 V AC as well, giving selectivity headroom for downstream coordination studies. Operating temperature range is -20 to +60 °C, with storage and transport tolerance from -50 to +80 °C. Temperature compensation is active across the full operating range, so the thermal trip curve stays within tolerance even in a hot panel. Screw-type terminals on the main circuit accept 2×(0.75 to 2.5 mm²) solid or stranded, or 2×4 mm². The screwdriver shaft diameter should be 5 to 6 mm, Pozidriv size 2.","metaTitle":"Siemens 3RV2011-0AA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-0AA10-ZX95 SIRIUS motor protection circuit breaker, Class 10 trip, S00 frame, 45 mm wide, 97 mm deep. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2011-0AA10-ZX95","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for motor protection, CLASS 10 A-release 0.11...0.16 A N-release 2.1 A screw terminal Standard switching capacity Reusable packaging Pack = 43 units","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.16 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.16 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.16 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.16 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"2.1 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.11 ... 0.16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/63b1c442f9af3979117ce06cd74d03a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=79860&mlfb=3RV2011-0AA10-ZX95"},"ai":{"faq":[{"question":"What is the depth of the 3RV2011-0AA10-ZX95?","answer":"The depth is 97 mm. Combined with the 45 mm width and 97 mm height, the unit fits standard S00 frame panel cutouts."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0AA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0AA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}