{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0BA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0BA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0BA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0BA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, size S00, for motor protection, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting on 35 mm DIN rail, order code 3RV2011-0BA10-ZX95.","salesMarkdown":"Its job is to combine a circuit breaker's short-circuit interruption with a thermal overload relay's motor protection curve — one device, one DIN-rail footprint, no separate overload relay needed downstream. At 240 V AC it's also 100 kA. For most industrial distribution panels with a transformer upstream, that's enough SCCR headroom to avoid a cascading failure. Size S00 means a 45 mm width, 97 mm depth, 97 mm height. That keeps heat dissipation and arc-flash clearance predictable in a crowded panel. Terminals are M3 screw-type for the main current circuit, accepting 2×(0.75…2.5 mm²) or 2×4 mm² solid/stranded. Pozidriv size 2 tip, screwdriver shaft diameter 5 to 6 mm. Strip length and torque aren't listed here, but the M3 terminal class is standard for this frame size. The 100 kA rating holds at 500 V and 690 V too, so it works on 480 V and 600 V class systems without derating the interrupt rating. Trip Class 10 and phase failure detection mean this breaker is tuned for motor starting duty, not just resistive load protection. If you're protecting a motor that takes longer than 10 seconds to start (high-inertia loads like centrifuges or large fans), Class 10 may nuisance-trip — you'd want Class 20 or 30. For standard industrial motors, Class 10 is the default.","metaTitle":"Siemens 3RV2011-0BA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV2011-0BA10-ZX95 motor protection circuit breaker, size S00, Class 10 trip, 100 kA breaking capacity at 400 V. Current production, available to order. Quoted on re","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.2 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.2 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.2 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.2 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.2 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"2.6 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.14 ... 0.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e6c326c7985ac9bb0baaa7c7f3c66ef8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=106889&mlfb=3RV2011-0BA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0BA10-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2011-0BA10-ZX95?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"Will 3RV2011-0BA10-ZX95 drop into a panel wired for 3RV2011-0BA20?","answer":"Both are size S00 on 35 mm DIN rail with the same 45 mm width and M3 screw terminals, so the mechanical fit and wiring are identical. The difference is in the internal trip settings and accessories — verify the overload range of the -0BA20 against your motor FLA before swapping."},{"question":"What is the depth of 3RV2011-0BA10-ZX95?","answer":"Listed depth is 97 mm. Width is 45 mm, height is 97 mm. Clearance: 50 mm above and below, 30 mm to the side."},{"question":"What compliance documentation does this part carry?","answer":"The evidence does not list specific certifications (UL, CSA, CE, RoHS, REACH) for this exact order code. For a BOM freeze or export compliance check, request the manufacturer's declaration with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0BA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0BA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}