{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0DA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0DA15","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0DA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0DA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-0DA15 motor protection circuit breaker, CLASS 10 trip, 100 kA breaking capacity at 400 V, phase failure detection, screw-type terminals, 45 mm wide, DIN rail mount.","salesMarkdown":"It combines a CLASS 10 trip curve with phase failure detection, meaning it will disconnect a motor within 10 seconds at 7.2× rated current and also trip if one phase drops out — a common failure mode that cooks windings. Rated operating voltage spans 20 to 690 V, and the unit delivers 100 kA breaking capacity at 400 V, which is enough to handle high-fault-current industrial panels without cascading upstream. The 45 mm width is a standard 2.5 module footprint — fits alongside contactors in a typical motor starter combo. Any mounting position is allowed. Main circuit terminals are M3 screw-type, accepting 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²). Keep the strip length clean; the M3 screws need a proper torque to avoid hot spots at full load.","metaTitle":"Siemens 3RV2011-0DA15 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2011-0DA15 SIRIUS motor protection circuit breaker. CLASS 10 trip, 100 kA breaking capacity at 400 V, phase failure detection. DIN rail mount. Current lifecycle: active.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.32 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.32 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.32 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.32 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.32 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"4.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.22 ... 0.32 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$35.56","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=71400&mlfb=3RV2011-0DA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0DA15/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV2011-0DA15?","answer":"The breaking capacity is 100 kA at 400 V AC, and also 100 kA at 240 V, 500 V, and 690 V — consistent high-fault performance across the voltage range."},{"question":"Will 3RV2011-0DA15 drop into a panel specified around 3RV2011-0AA10?","answer":"Both share the same SIRIUS 3RV20 family footprint — 45 mm wide, DIN rail snap-on, same terminal specs — so it should fit mechanically without rewiring. Verify the trip class and current rating match your motor nameplate before swapping."},{"question":"How do I get current pricing and availability for 3RV2011-0DA15?","answer":"Submit an RFQ through this listing. The part is sourced to order via independent distribution; pricing and stock levels are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0DA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0DA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}